16 Operating Parameters
16.6 Administrative
429
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
16.6.5.3 Mapping – Indications
Parameter
Default Setting
Setting Range
Name
Indication x Slv 1
(x = 1 to 15)
Max. 31 characters
Register type
-none-
-none-
Coil status registers
Input status registers
Input registers
Holding registers
For
-none-
,
the assignment is ignored
and the corresponding indication cannot
be selected for other functions.
Data format on bus
(See following table.)
1 Bit
1 Bit
1 Bit in UInt32
Data format which is used to transmit the
indication via Modbus
Register number
1
1 to 65 535
Bit offset
(only relevant for register types
Input register or Holding register)
0
0 to 15 (for Data format 1 Bit)
0 to 31 (for Data format 1 Bit in UInt32)
depending on selection for
Data format
on bus
)
Data Format on Bus
Description
Setting Range
Invalid recognition
1 Bit
1 bit (for all register types; addition-
all select
Bit offset
for Input regis-
ter and Holding register)
0 = of
1 = on
none
1 Bit in UInt32
1 bit in 2 successive Input registers
or Holding registers which have to
be read together.
0 = of
1 = on
none