9 Operation at Use of a PC
9.2 Start and Design of the User Interface
139
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
9.2
Start and Design of the User Interface
9.2.1
Initial Start of the Operation
Before starting the user interface, the following preconditions must be satisfied:
✧
Assemble the SICAM Q100 as described in chapter 7.2.
✧
Connect the lines for measurement, communication and supply voltage as described in chapter 7.3 and
observe the safety provisions.
✧
Switch on the devices needed for the measurement.
✧
Switch on the supply voltage of the SICAM Q100.
✧
Check whether the LEDs at the SICAM Q100 indicate that the device is ready (see chapter 13.2).
✧
Match the IP address and the subnet mask of the network interface card of your computer to the device
settings.
✧
Check on the computer screen whether the LAN connection is up. Activate the LAN connection if it is down
(see the Windows manual or the Windows online help for information).
✧
For checking purposes, carry out the ping test as follows (example for Windows):
Click
Start
on the Windows interface.
Select
Execute...
.
Enter
cmd
in the dialog and click
OK
.
Enter:
ping 192.168.0.55
.
Press
ENTER
.
Check the following output in the window.
Figure 9-1
Ping Test
✧
Start the Web browser.
✧
Enter the IP address in the Web browser (for example default IP address: https://192.168.0.55) of
SICAM Q100 and press
ENTER
.
The user interface opens with the
Information
tab ->
Show device information
(see Figure 9-8).