16 Operating Parameters
16.6 Administrative
427
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
16.6.5.2 Mapping – Measured Values 1 – 15
Parameter
Default Setting
Setting Range
Name
MV x Slv 1
(x = 1 to 15)
Max. 31 characters
Max. 10 characters if the name is also to
be displayed on the device display.
Unit
Note on frequency measured
values:
If a frequency measured value
(unit: Hz) has been parameterized
without a multiplier (multiplier: -), an
additional check is made whether
the resulting value is in the range of
15 Hz to 65 Hz. Measured values
outside this range are marked as in-
valid.
Note on factors:
Selecting a multipier for the follow-
ing units is not recommended and
will be rejected: -none-
°
°C
°F
%
Multiplier: -
m (milli)
c (centi)
d (deci)
-
h (hecto)
k (kilo)
M (Mega)
G (Giga)
Unit: -none-
-none-
m
kg
s
A
°C
V
Hz
W
Pa
m
2
m
3
VA
var
°
Wh
VAh
varh
%
°F
Register type
-none-
-none-
Input registers
Holding registers
For
-none-
,
the assignment is ignored
and the corresponding measured value
cannot be selected for other functions.
Data format on bus
(See following table.)
Float32 (2 registers)
Float32 (2 registers)
Int16 (1 register)
Int16_Ung8000h (1 register)
UInt16 (1 register)
UInt32 (2 registers)
Register number
1
1 to 65 535
Scaling factor
1.000
Any float value
0.00: resulting measured value = 0.00
MAN_SICAM_Q100_US.book Page 427 Wednesday, June 5, 2019 9:31 AM