10 Operation at Use of the Display
10.4 Parameterization
350
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
1)
Separate CT In
is available only if the following
Connection type
is selected: 3P4W (four-wire, any load).
Use PTs:
PT primary
PT secondary
AC 10 000 V
AC 100 V
AC 100 V to 1 000,000 V
AC 1 V to 460 V
Primary nominal voltage
(Phase-N/PE)
230.00 V
AC 57.73 V to 400 V (autorange)
IEC 61000-4-30 Class A: to AC 230 V:
200 % overvoltage
> AC 230 V to 400 V: 200 % to 15 %
overvoltage
UL conditions:
to AC 170 V: 200 % overvoltage
> AC 170 V to 300 V: 200 % to 15 %
overvoltage
Current Inputs
Use CTs?
No (no checkmark)
Yes (checkmark)
No (no checkmark)
Use CTs:
CT primary
CT secondary
Separate CT In
1)
?
AC 1 000.00 A
AC 1.00 A
No (no checkmark)
AC 1.0 A to 100 000.0 A
AC 1.0 A to 10.00 A
Yes (checkmark)
No (no checkmark)
Separate CT In?
CT Primary In
AC 1 000.00 A
AC 1.0 A to 100 000.0 A
Zero-Point Suppression
Zero-point suppression
(in % of Vrated
and Irated)
0.3 %
0.0 % to 10.0 %
Table 10-3
Basic Parameter Settings (cont.)
Parameter
Default Setting
Setting Range
MAN_SICAM_Q100_US.book Page 350 Wednesday, June 5, 2019 9:31 AM