9 Operation at Use of a PC
9.3 Configuration of the Device
253
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Server IP address
192.168.0.57
any
(different from IP address of subde-
vice 1 and in the same subnet as
SICAM Q100)
Server port
51 000
10 000 to 65 535
Response timeout
3 (* 10 ms)
10 ms to 60 000 ms
0 ms = invalid
Parameter: Source of output 1-N
Indication: Input 1-N
Indication 9 from Remote
Binary inp. 1-N SICAM IO 2
Indication: any, max. 31 characters
Parameter Source of output:
Selection which indication is trans-
mitted from SICAM Q100 to the
binary output of the SICAM I/O Unit
7XV5673.
Indication Input:
Designation of the indication which
shows the status of the binary input
of SICAM I/O Unit 7XV5673.
Parameter: Source of output 2-N
Indication: Input 2-N
Indication 10 from Remote
Binary inp. 2-N SICAM IO 2
Parameter: Source of output 3-N
Indication: Input 3-N
Indication 11 from Remote
Binary inp. 3-N SICAM IO 2
Parameter: Source of output 1-P
Indication: Input 1-P
Indication 12 from Remote
Binary inp. 1-P SICAM IO 2
Parameter: Source of output 2-P
Indication: Input 2-P
Indication 13 from Remote
Binary inp. 2-P SICAM IO 2
Parameter: Source of output 3-P
Indication: Input 3-P
Indication 14 from Remote
Binary inp. 3-P SICAM IO 2
Table 9-38
Settings of the SICAM Subdevices (cont.)
Parameter/Indications
Default Setting
Setting Range