9 Operation at Use of a PC
9.3 Configuration of the Device
192
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
9.3.6
Recording and Reporting
In the
Configure
tab, you can view and, if necessary, edit the settings for recording and reports. You can select
these parameters in the
Recording and reporting
menu in the navigation window. The menu contains the fol-
lowing elements:
•
Event recorder
•
Trigger management
•
Recorder parameters
•
Mains signaling voltage
•
Memory management
•
Report configuration
•
Recording parameters
•
Transient detection
9.3.6.1 Event Recorder
Default Settings and Setting Ranges
Table 9-14
Event Recorder
Parameter
Default Setting
Setting Range
Voltage event
Swell threshold
110 %
105 % to 140 % in 5-% steps
Dip threshold
90 %
75 % to 95 % in 5-% steps
Interruption threshold
5 %
1 %, 2 %, 3 %, 5 %, 8 % 10 %
Hysteresis
2 %
1 % to 6 % in 1-% steps
Event detection mode
1)
ph-N
ph-N
ph-ph
RVC event
RVC threshold
6 %
1 % to 6 % in 1-% steps
RVC hysteresis
2)
3 %
0.5 % to 3 % in 0.5-% steps
RVC event detection mode
3)
ph-N
ph-N
ph-ph
Frequency event
Underfrequency threshold
1 %
0.1 % to 1.0 % in 0.1-% steps and
1.0 % to 5.0 % in 1.0-%-steps