9 Operation at Use of a PC
9.3 Configuration of the Device
153
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
9.3
Configuration of the Device
9.3.1
Device Configuration Procedure
If you have not changed the set of parameters since the first start of the device (see chapter 9.2.1), use the
factory settings (see chapter 9.3.3 to chapter 9.3.7). To change the settings of the set of parameters, proceed
as follows:
✧
Click the
Configure
tab on the user interface.
Figure 9-14
Configure Tab
✧
Select the
Prepare
menu in the navigation window and then either
Get device configuration
or
Open
configuration from file
.
NOTE
The device contains two sets of parameters. The set of parameters currently used for device operations is the
active set of parameters
. The inactive set of parameters is called the
passive set of parameters
.
The following sections describe how to change and enable the passive set of parameters.
NOTE
If you have selected
Get device configuration
, an editable copy of the active parameter set of the device is
displayed on the screen. In the meantime, the active parameter set in the device continues to operate.
If you have selected
Open configuration from file
, you can open and enable or edit the copy of a parameter
set that was already created and saved to a folder.
MAN_SICAM_Q100_US.book Page 153 Wednesday, June 5, 2019 9:31 AM