
9 Operation at Use of a PC
9.3 Configuration of the Device
250
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Description and setting ranges of the parameters in the text file:
Table 9-37
Description and setting ranges of the parameters in the text file.
Label
Measured
Quantity (MV)
Indication (I)
Description
Setting Range
MT
MV
M
apping
T
ype
(Data type)
MEASURAND
INDICATION
DS
MV, I
D
e
s
cription
Name of the associated data object
String with max. 31 characters
Longer strings are cut at 31 cha-
racters during import.
RN
MV, I
Register number
(within the selected register type
RT)
1 to 65 535
RT
MV, I
R
egister
t
ype
0x0 – Coil status register
0x1 – Input status register
0x3 – Input register
0x4 – Holding register
OF
I
B
it
o
ffset
(for INDICATION in Holding regis-
ters)
0 to 15 (for FT = 1BIT)
0 to 31 (for FM = 1BITINUINT32)
FM
MV, I
Data
f
or
m
at
For MEASURAND:
FLT32, INT16, UINT16, UINT32,
INT16INV7FFF and INT16INV8000
For INDICATION:
1BIT, 1BITINUINT32
SC
MV
Sc
aling factor for MEASURAND
Arbitrary float value
UN
MV
Un
it-multiplier for MEASURAND
1: dimensionless
2: Meter
3: kg
4: s
5: A
23: °C
29: V
33: Hz
38: W
39: Pa
41: m
2
42: m
3
61: VA
63: var
64: °
71: VAh
72: Wh
73: varh
75: %
76: °F
MAN_SICAM_Q100_US.book Page 250 Wednesday, June 5, 2019 9:31 AM