16 Operating Parameters
16.2 Automation Functions
405
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
16.2.1
Limit Violation 1-8 and 9-16
1)
31 bytes of UTF-8
Parameter
Default Setting
Setting Range
Measurement
-none-
-none-
Va, Vb, Vc
Vab, Vbc, Vca
Ia, Ib, Ic
VN, Vavg
IN, Iavg
Pa, Pb, Pc, P
Qa, Qb, Qc, Q
Sa, Sb, Sc, S
cos
(a), cos
(b), cos
(c), cos
PFa, PFb, PFc, PF
UIa,
UIb,
UIc,
UI
f
Neg.seq.comp.V
Neg.seq.comp.I
THDS Va, THDS Vb, THDS Vc
THDS Vab, THDS Vbc, THDS Vca
THDS Ia, THDS Ib, THDS Ic
ab V,
bc V,
ca V
ab I,
bc I,
ca I
Q1a, Q1b, Q1c; Q1
Pinst (a-n), Pinst (b-n),Pinst (c-n)
Pst (a-n), Pst (b-n),Pst (c-n)
Plt (a-n), Plt (b-n),Plt (c-n)
Pinst (a-b), Pinst (b-c), Pinst (c-a)
Pst (a-b), Pst (b-c), Pst (c-a)
Plt (a-b), Plt (b-c), Plt (c-a)
Zero seq.comp.V
Zero seq.comp.I
MV x from Bus device y
*)
(x = 1 to 15 and y = 1 to 8)
(Setting ranges pending from network type)
*)
Designation can be changed during the
parameterization.
Limit
0.00
-1 000 000 000 to 1 000 000 000 (unit)
Limit type
Lower
Lower
Upper
Hysteresis (%)
1.0
0.0 to 10.0
Violation indication
Limit Violation x
(x = 1 to 16)
Any
Max. 31 characters
1)
MAN_SICAM_Q100_US.book Page 405 Wednesday, June 5, 2019 9:31 AM