Approvals, certificates, standards
9.5 XR-300M EEC product group
SCALANCE X-300
Operating Instructions, 05/2016, A5E01113043-20
251
ATEX (explosion protection directive)
WARNING
When using SIMATIC NET products in hazardous area zone 2, make absolutely sure that
the associated conditions in the following document are adhered to:
"SIMATIC NET Product Information Use of subasseblies/modules in a Zone 2 Hazardous
Area".
You will find this document
•
on the data medium that ships with some devices.
•
on the Internet pages of Siemens Industry Online Support
http://support.automation.siemens.com/WW/view/en
Enter the document identification number C234 as the search term.
SIMATIC NET products meet the requirements of the EC directive:94/9/EC "Equipment and
Protective Devices for Use in Potentially Explosive Atmospheres".
ATEX classification:
II 3 G Ex nA IIC T4 Gc
KEMA 07ATEX0145 X
The products meet the requirements of the following standards:
●
EN 60079-15: 2010 (electrical apparatus for potentially explosive atmospheres; Type of
protection "n")
●
EN 60079-0: 2009 (Explosive atmospheres - Part 0: Equipment - General requirements)
Note
Only variants with 24 VDC power supply meet the requirements of this approval.
IECEx
The SIMATIC NET products meet the requirements of explosion protection according to
IECEx.
IECEx classification:
Ex nA IIC T4 Gc
DEK 14.0025X
The products meet the requirements of the following standards:
●
IEC 60079-15 : 2010 (Explosive atmospheres - Part 15: Equipment protection by type of
protection "n"
●
IEC 60079-0 : 2011 (Explosive atmospheres - Part 0: Equipment - General requirements)