Example of an FTP client configuration file
# This is a comment
TIMESTAMP=
3D2C4E48
FILETYPE=FDB
FILEFORMAT=01
00|
W
|
1
|
VB0
|
station99_VB0_1.dump|192.168.232.13|FTP_Server_2|3AqW&4Cv
01|
W
|
1024
|
VB256
|
/station36_VB256_1024.data|192.168.232.13|FTP_Server_2|3AqW&4Cv
02|
R
|
5
|
VB2
|
/data/station36_VB2_5.err|192.168.232.2|FTP_Server_3|asw345Df
03|
R
|
23
|
VB11|/flash:/dat/CPU10_VB11_23.dat|192.168.162.65|
FTP_Server_4|
W9vQ}G cfH
04|||||||
05|||||||
06|||||||
07|
D
|||
/data/station36_VB2_5.err|192.168.232.2|FTP_Server_3|asw345Df
08|||||||
.....
30|||||||
31|||||||
END
# End of File
Note
−
Commentary is added to the file with the # character.
−
A blank user entry in the .fdb file is stored as follows:
xx
||||||| (whereby xx
stands for the running FTP client job number)
−
The last character of a line is \n.
−
All characters between 0x21
HEX
and 0x7E
HEX
can be used for path, file
name, user name and password if this is acceptable to the communication
partners involved.
−
The following additional restrictions apply to directory and file names.
Not supported: blanks ; \ ; / ; | ; < ; > ; “ ; : ; * and ?
−
Blank lines are not permitted.
Caution
With a READ action,
<Number of bytes>
is usually between 0 and 10240 (maxi-
mum with the CPU 226XM).
When the value 0 is entered, the CP 243-1 IT does not check the actual file length.
All data in the file are read and, starting with
<DB start address>
, copied to the DB
of the S7-200 CPU if this does not exceed the memory size.
If the number of data bytes to be read is not 0, the CP 243-1 IT checks during the
data transmission to determine whether the specified number of bytes has already
been reached and, if so, concludes the copy procedure. This procedure offers a
high degree of security and protects the unsecured memory area of the S7-200
CPU from being overwritten accidentally.
Содержание CP 243-1 IT
Страница 46: ...Installation and Commissioning 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 46 ...
Страница 94: ...Programming 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 94 ...
Страница 106: ...Diagnosis 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 106 ...
Страница 120: ...Technical Data 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 120 ...
Страница 130: ...Example 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 130 ...