1. FEATURES

2. UNIQUE FEATURES

M1M 10

L1

L2

L3

L1

L2

L3

L1

Warning!

 Installation by person with

electrotechnical expertise only.

6.1. Star connection (3E) 3 phase 4 wire system

6.2. Delta connection (2E) 3 phase 3 wire system

6. WIRING DIAGRAM

6.3. Single phase connection

Note:

  Wiring should be in accordance with the National Electrical Code and/or

the Canadian Electrical Code, Part I.

For DC AUX Voltage, +/-ve can be connected anyway.

3. KEY FUNCTIONS

ABB India Limited

88/3, 88/6, Basavanahalli,
Nelamangala Taluk,
Bengaluru - 562123
Karnataka  INDIA
www.abb.com

Contact us

STAR (Wye)/ DELTA/1 phase programmable

Universal Auxiliary (80 - 300 VAC / DC) supply

PT ratio / CT ratio programmable including CT secondary

User configurable (editable) password

Simultaneous sampling of Volts & Amps

True RMS measurement

Universal Voltage Input (50 - 550 VAC) and 

Current Secondary (0.05 to 6A)

Optional Programmable relay output maximum 2 

(up to 6 threshold     parameters) and tripping time up to180 
seconds.

3 row, 4 digit display for better readability.

Auto-scaling of kilo & mega, decimal point.

Compact size and weight

KILO – ON

Kilo

Direct reading

KILO – OFF

Voltage line to line

VLL - ON

Voltage line to Neutral

VLN - On

Amps

A - ON

Frequency

Hz - ON

4. LED INDICATIONS

Enabling auto scrolling: Press UP key continuously for 5 seconds or until 
display  shows 

EnbL  Auto.Sc

  for  upward  scrolling.  Press  Down  key 

continuously  for  5  seconds  or  until  display  shows 

EnbL  Auto.Sc

  for 

downward scrolling.

Disabling auto scrolling: Press any key (UP/DOWN), display show

 dSbL 

Auto.Sc

 and returns to normal mode.

5. ENABLING AND DISABLING

10

Press DOWN key 

Row 1: xxxx 

(415.0 -default

/factory set) 

Row 2: P. Pri(PT Primary)

7. CONFIGURE (SETUP MODE)

To configure the setup parameters through front panel, the following 
steps can be followed.

1

6

Press UP & DOWN 
keys together to enter 
SETUP

Press DOWN key 

Row 1: 0000 

with first digit 

“0” blinking

Row 2:SEtP  (SETUP) 

Press UP key 

3

                        Display
will prompt to    . Press
UP key to change to 

Press UP key 

4

SETUP MODE

CLEAR MODE (Only 1310)

2

Press DOWN key 
to decrement the first digit 
to “9”  sequentially come 
to digit “1”

Row 1: 1000 

with first digit 

“1” blinking

Row 2:SEtP  (SETUP) 

Press DOWN key to 
decrement the first digit
to ‘9’ sequentially
come to digit ‘.1’

Option: YES/NO
“Y” for clearing. “n” for not
clearing

                  Row 2: Display
will prompt to    . Press
DOWN key to change to 

5

Press UP key 

Row 1 : xxxx
Row 2 : xxxx
Row 3 : xxxx

8

9

Press UP key to select
STAR/DELTA/1. PHASE

Press UP key to 

accept 

the selected  mode

Row 1: StAr/ 

dELt/ 1.Phase

Row 2: ELEm

Options can be changed 

by pressing DOWN key.

Row 1: StAr/ 

dELt/ 1.Phase

Row 2: ELEm

selected system blinks

Selected system 
stabilizes

7

Press UP key four times 
to accept the password.

Row 1:  StAr

Row 2: ELEm 

(ELEMENT)

Defines the power 
system configuration. 
Options: STAR /DELTA/
SINGLE PHASE

Default password
‘1000’.

11

12

Press UP key to set 
the PT primary value

Press UP key to 

accept

 

the edited value for 
first digit.

Row 1: First 

digit blinks.Edit 

the digit using DOWN key.

Row 2 : P. Pri (PT Primary)

Row 1: Second 

digit blinking, 

can be edited using DOWN key. 

Press UP key to accept the
 edited value. Continue the

same method till fourth digit.

Row 2 : P. Pri (PT Primary)

Program Range for PT 
Primary : 100V to 999kV
Comment: If value set is 
above the limit, display 
returns to maximum 
PT Pri value.

13

Press UP key.

  Row 1:Decimal 

point blinking. 

Can be set at appropriate 

location using DOWN key. 

Ascertain the correct scale

(Kilo/Mega) is selected by 

Letter K/M. Press UP key to 

accept the edited value.

Row 2 : P. Pri (PT Primary)

E.g.: To set 11.00kV
Set first four digits

(1100)

as 

explained above keep 
pressing DOWN key to 
place decimal point at 
appropriate location. 
Letter K/M will indicate 
the Kilo/Mega.

16

17

Press DOWN key 

Press DOWN key 

Row 1: xxxx 

(5.000-default/

factory set) 

Repeat steps 7 to 13 to 

change the settings.

Row 2: C. Pri (CT Primary)

Row 1: xxxx 

(5.000 –default 

/ factory set)

   Row 2: C.SEC 
(CT Secondary).

Program Range for CT 
Primary 0.5A to 99kA

Range: 0.5A to 6A

Repeat steps 7 to 13.

14

15

Press UP key.

Press DOWN key 

  Row 1:Decimal 

point blinking. 

Can be set at appropriate 

location using DOWN key. 

Ascertain the correct scale

(Kilo/Mega) is selected by 

Letter K/M. Press UP key to 

accept the edited value.

Row 2 : P. Pri (PT Primary)

Row 1: xxxx 

(415.0 -default

/factory set)                   

Row 2: P.SEC 

(PT Secondary).

 Follow the procedure as 

described in steps 7 to 13.

E.g.: To set 11.00kV
Set first four digits

(1100)

as 

explained above keep 
pressing DOWN key to 
place decimal point at 
appropriate location. 
Letter K/M will indicate 
the Kilo/Mega.

Range: 50V to 550V
If value set is above the 
limit, display returns to 
the maximum PT 
sec value.

Input: 1A/5A / 300V L-N 50/60Hz

Input: 1A/5A / 300V L-N 50/60Hz

Input: 1A/5A / 300V L-N 50/60Hz