ABB M1M 10 Скачать руководство пользователя страница 2

CT Primary (C.Pr

ı

)

5.000

0.5A - 99kA

4

CT Secondary (C.SEC)

5.000

0.5A - 6A

5

Sl.No.

Parameter

Default 

setup

Range / Options

Connection mode(ELEm)

PT Primary (P.Pr

ı

)

PT Secondary (PT SEC)

STAR

415.0

415.0

STAR/ DELTA/ 1.Phase

100V- 999kV

50V - 550V

1

2

3

7

6

Password (PWd)

No of Poles (POLES)

1000

      4.000

1000 to 9999

1.000 to 28.00

8

Voltage Suppression 

      15.00

10.00 to 80.00

18

Press Down key

Range: 1000-9999.
CAUTION:  Password can 
be reset only 
at the factory.

 

CAUTION

:

 memorize  the 

Password.Use  the  same 
Password  for  next  time. 
Instruments  will  reject 
other Passwords.

19

20

Press DOWN key

Press DOWN key

Row 1: 4.000

Row 2: POLS

(POLES)   

Range: 1-28 (FOR RPM).
 

Row 1: ----

Row 2: PWd 

(Password 

user  definable).

21

Press DOWN key

Row 1:  S A V E  

Row 2:  “Y” 

blinking

If “n”(no) is selected then 
Meter enters into RUN 
mode without affecting any 
edited Values in the setup

Row 1: 15.00

Row 2: voltage

suppression  

Range: 10-80.
 

22

Press DOWN key

Row 1 : xxxx
Row 2 : xxxx
Row 3 : xxxx

Once the required parameter is programmed press the DOWN key continuously till it 
reaches SAVE page directly.

8. MECHANICAL SPECIFICATION

Auxiliary power supply

Range

Burden

Frequency

80V to 300 V AC or DC

5VA Max

50 - 60Hz

Installation category
Protection fuse

CAT III
200mA

Measurement accuracy

Voltage 
Current 

±1,0%
±1,0%

Voltage measurement inputs

Measurement range

Rated frequency

Measurement category

80-300V AC (p-n)

50 - 60Hz

CAT III

Max. VT Primary

999 Kv

Burden

0.2VA Max. per phase

Mechanical characteristics

Overall dimensions

IP degree of protection

96 X 96 X 58 mm (52 mm depth
inside the switchboard)
IP51 (IEC 60529)

Weight

0,300 kg

Climatic conditions

Operating temperature
Storage temperature

-10°C to +60°C
-25°C to +70°C

Relative humidity

5% to 95% non condensing

Pollution degree
Altitude

2
Below 2000ms

Terminal characteristics

Current inputs 

Voltage inputs 

6 terminals, 3 inputs, 5A with
S1 and s2 on each input

4 terminals. 80-520V LL

Standards

Electrical safety
EMC

IEC 61010
IEC 61000 4-2,4-3,4-6,4-8,4-4,4-11,
CISPR-22

Current measurement inputs

Number of current inputs

Measurement range without
accuracy derating

CT secondary

3 (L1, L2, L3)
1A or 5A  

Max. CT Primary

99 kA

Burden

0.2VA Max. per phase

50mA-6A (5%-120% as per standard.
From 50mA onwards, it will measure)

User Interface

Access to device
Display type

2 pushbuttons
LED display

LED Digit height 

10 mm

9. TECHNICAL SPECIFICATION

96

96

52

90

90

+2

90

-0

+2

90

-0

M1M 10

Note:

Accuracy class note for current: 

For input current below 250mA, additional

error of 0.1% of full scale.

o

Accuracy class error for Temperature: 

Below 10 C, mean temperature

coefficient for the meter is 0.15%/K

Отзывы: