Programming
03/03
CP 243-1 IT
J31069-D0429-U001-A0-7618
102
Call:
ETHx_EMAIL
START
EN
DONE
Done
ERR
Error
Abort
ABORT
Always_On
START_BIT
Fig. 12
Call of the subprogram ETHx_EMAIL
Input parameters:
Name
Type
Meaning
START
BOOL
Input condition for triggering an e-mail job
0:
Don't trigger e-mail job
1:
Trigger e-mail job
BYTE
Number of the e-mail from the configuration
which describes the e-mail job to be executed
Value range: 0 to 31
Abort
BOOL
Input conditions for canceling an e-mail job
0:
Don't cancel e-mail job
1:
Cancel e-mail job
Table 23
Input parameters (ETHx_EMAIL)
Return parameters:
Name
Type
Meaning
Done
BOOL
Status of the subprogram call
0:
Subprogram not executed yet
1:
Subprogram executed, e-mail job con-
cluded, subprogram ready for next exe-
cution.
Error
BYTE
Error code
16#00: No
error
Other: Error (for a description, see chapter
6.2)
Table 24
Return parameters (ETHx_EMAIL)