5.2 ETHx_CFG
Calling the subprogram ETHx_CFG causes the CP 243-1 IT to read in the configu-
ration data which are stored in the memory of the S7-200 CPU. The CP 243-1 IT
then automatically performs a reset after the subprogram ETHx_CFG is called. The
configuration read from the memory of the S7-200 CPU takes effect after the re-
start following the reset.
You will need this subprogram if you want to reconfigure a CP 243-1 IT dynami-
cally from this program while your S7-200 user program is running. This program is
only created by the Internet wizard on STEP 7 Micro/WIN 32 when the CRC rou-
tine is not activated there for your configuration. When the subprogram ETHx_CFG
is called, the CP 243-1 IT terminates all existing connections and performs a reset.
As soon as the CRC routine is activated, however, you can no longer change the
configuration from a user program. This is then only possible via the Internet wiz-
ard in STEP 7 Micro/WIN 32.
Call:
ETHx_CFG
START
EN
Always_On
DONE
Done
START_BIT
ERR
Error
Fig. 10
Call of the subprogram ETHx_CFG
Input parameters:
Name
Type
Meaning
START
BOOL
Input conditions for triggering a new configura-
tion
0:
Don't trigger new configuration
1:
Trigger new configuration
Table 19
Input parameters (ETHx_CFG)
Содержание CP 243-1 IT
Страница 46: ...Installation and Commissioning 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 46 ...
Страница 94: ...Programming 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 94 ...
Страница 106: ...Diagnosis 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 106 ...
Страница 120: ...Technical Data 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 120 ...
Страница 130: ...Example 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 130 ...