Diagnosis
03/03
CP 243-1 IT
J31069-D0429-U001-A0-7618
112
The next few sections list the error codes for the individual errors together with
their meaning. Also covered: how the individual errors are returned, which error
codes apply to which subprograms, and which error in which byte of the current
SM memory area is transferred. If error messages occur which are not described in
these sections, please contact your service hotline.
If these next few sections do not provide a solution, manual correction of the errors
via STEP 7 Micro/WIN 32 is always required. The Internet wizard of STEP 7 Mi-
cro/WIN 32 should always be used to configure the CP 243-1 IT.
If your CP 243-1 IT returns errors indicating a problem with the configuration,
check to determine whether your user program may have overwritten the configu-
ration.
Caution
During power failures (24 V), the CP 243-1 IT is unable to return any more error
messages.
6.2.1
Error Messages in Byte Format
Error Byte
Transfer Rou-
tine
Hex Dec
Description Reaction/Correction
Byte
Offset
in SM
Area
Return
Value
(ETHx_)
16#01 1
Time exceeded on the backplane
bus
Automatic restart
25 - 32
33
34
35
_XFR
_CFG
_EMAIL
_FTPC
16#02 2
Data access terminated due to an
ABORT command.
A new read/write job can be
started.
25 - 32
34
35
_XFR
_EMAIL
_FTPC
16#03 3
The transfer parameter DATA or
MAIL or OP is outside the config-
ured area.
Check user program or configu-
ration.
25 - 32
34
35
_XFR
_EMAIL
_FTPC
16#04 4
The connection could not be set up
at the S7 level.
The attempt to establish a con-
nection is repeated.
25 - 32 _XFR
Содержание CP 243-1 IT
Страница 46: ...Installation and Commissioning 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 46 ...
Страница 94: ...Programming 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 94 ...
Страница 106: ...Diagnosis 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 106 ...
Страница 120: ...Technical Data 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 120 ...
Страница 130: ...Example 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 130 ...