Features and Functions
03/03
CP 243-1 IT
J31069-D0429-U001-A0-7618
36
HTML Page Call
Meaning
http://<destination IP ad-
dress>/examples/info.htm
General information page of the CP 243-1 IT with ex-
ternal links to the IT CP and SIMATIC NET Web page.
An internal link refers to the Web page readme.htm.
http://<destination IP ad-
dress>/examples/statuschart.htm
This page can be used to read process values of the
S7-200 system.
The data or data areas to be read are designated by
address.
Remember that the values shown on this page are
read out cyclically. Depending on the cycle time, an in-
dicated value may differ from the value actually in the
S7-200 system at the same time.
Table 1
Predefined HTML pages
Note
Some of the HTML pages included with the CP 243-1 IT link in Java Applets. To
ensure that this functions correctly, the execution of Java Applets must be enabled
on the Web browser.
Communication partners
All HTTP clients (e.g., Web browsers) represent potential communication partners
of the HTTP server. The HTTP server of the CP 243-1 IT supports simultaneous
access of up to 4 Web browsers.
The TCP/IP connection to the HTTP server is always handled by port 80.
Performance/general conditions
On the CP 243-1 IT, HTTP communication is subordinate to S7 communication.
Reaction times vary with the particular configuration and cannot be predicted gen-
erally in advance.
The HTTP server located on the CP 243-1 IT has four communication channels
(i.e., it can process up to four requests at the same time). When a request arrives
at the HTTP server when all four communication channels are occupied, the re-
quest is rejected. New requests cannot be processed until at least one of the four
communication channels is free again.
Содержание CP 243-1 IT
Страница 46: ...Installation and Commissioning 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 46 ...
Страница 94: ...Programming 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 94 ...
Страница 106: ...Diagnosis 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 106 ...
Страница 120: ...Technical Data 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 120 ...
Страница 130: ...Example 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 130 ...