Diagnosis
03/03
CP 243-1 IT
J31069-D0429-U001-A0-7618
108
Byte Offset in
SM Area
Meaning
Format
0-15
Module type
16 bytes,
ASCII
16-19
Software version
4 bytes,
ASCII
20-21
Error code (see chapter 6.2)
2 bytes, hex
22
Status CP 243-1 IT
Bit [0]
0: CP 243-1 IT not in startup
1: CP 243-1 IT performing startup
Bit [1]
0: BOOTP sequence not performed
1:
BOOTP
sequence
performed
Bit [2]
0: CP 243-1 IT not ready
1: CP 243-1 IT ready
Bit [3]
0: STEP 7 Micro/Win 32 not active
1: STEP 7 Micro/Win 32 active
Bit [4]
0: Configuration in acc. w. CDB
1: No valid configuration in CDB
Bit [5] Reserved
Bit [6]
0: No Ethernet connection
1: CP 243-1 IT connected with Ethernet
Bit [7]
0: No error on CP 243-1 IT
1: CP 243-1 IT in error state
1 byte, hex
23 Reserved
24
Hardware version
1 byte,
ASCII
Table 27
Addressing of global errors and module information
Содержание CP 243-1 IT
Страница 46: ...Installation and Commissioning 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 46 ...
Страница 94: ...Programming 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 94 ...
Страница 106: ...Diagnosis 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 106 ...
Страница 120: ...Technical Data 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 120 ...
Страница 130: ...Example 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 130 ...