03/03
Features and Functions
CP 243-1 IT
J31069-D0429-U001-A0-7618
35
HTML Page Call
Meaning
http://<destination IP address>/index.htm
Start page of the CP 243-1 IT with links to further in-
ternal and external HTML pages
If only <destination IP address> is specified on the
Web browser, index.htm is automatically opened.
http://<destination IP address>/__S7Sys/rack
Indicates the setup of the S7-200 destination system.
In addition, the available status information for each
module is shown.
This page is not automatically updated. To indicate the
present status of the S7-200 system correctly, this
page must be loaded again to the Web browser.
Note:
"Rack" is not an HTML page located physically in the
file system of the CP 243-1 IT. When the adjacent ad-
dress is called from a Web browser, the HTTP server
dynamically sets up an HTML page with the system-
specific information. The layout of this page cannot be
changed by the user.
http://<destination IP ad-
dress>/__S7Sys/sendmail.htm
Indicates a page with which a test e-mail can be sent
to a specified receiver. The address fields (TO, CC)
and the fields of the subject and the text are limited to
a maximum of 64 characters each.
When the page is called, the user is asked to authenti-
cate himself with a user name and a password.
Only the administrator is authorized to send a test e-
mail. The errors which can occur are described in
chapter 6.3.
http://<destination IP address>/__S7Sys/it_info
Present status of the CP 243-1 IT. This page indicates
data relevant to operation of the CP 243-1 IT. Some
examples are listed below.
•
Module name
•
Firmware and hardware version
•
Network parameters
•
Status of the Micro/WIN connection
•
Configuration and availability of S7, FTP and
e-mail connections
•
Information pertaining to the file system
This information is only provided to users authorized
by user administration. These users must authenticate
themselves with a user name and a password.
This page is not automatically updated. To correctly
indicate the present status of the CP 243-1 IT, the Web
browser must load this page again.
Note:
"It_info" is not an HTML page located physically in the
file system of the CP 243-1 IT. When the adjacent ad-
dress is called from a Web browser, the HTTP server
dynamically sets up an HTML page with the system-
specific information. The layout of this page cannot be
changed by the user.
Содержание CP 243-1 IT
Страница 46: ...Installation and Commissioning 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 46 ...
Страница 94: ...Programming 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 94 ...
Страница 106: ...Diagnosis 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 106 ...
Страница 120: ...Technical Data 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 120 ...
Страница 130: ...Example 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 130 ...