Basic system information
&
114
Building Technologies
A6V10225450_b_en_--
Fire Safety
2017.09.07
Alarm / CAC: Cerberus alarm concept
How does the
CAC work?
If the system is running in 'Manned' operating mode, automatic and manual call points will acti-
vate
different measures
in the event of an alarm.
F
unmanned
Operation mode
<Reset>
pressed
‘Minor incident’
<Acknowledge >
pressed
F
pressed
‘Emergency’
V1
läuft
V1 = 0
V2 = 0
manned
V2
läuft
<Alarm delay OFF>
- or -
Alarm
event
Local
alarm
General
alarm
Remote
alarm
Normal
operation
manned or
unmanned
'V1' alarm
acknowledge-
ment time
·
This is a countdown which is active for automatic fire detectors when the system is in
'Manned' operating mode.
·
Checks whether anyone has acknowledged the danger alarm within a pre-programmed time.
·
But if this time passes without acknowledgement, the alarm is transmitted to the fire brigade.
·
The time remaining is shown on the display in minutes and seconds.
'V2' alarm inves-
tigation time
·
This is a countdown which is active for automatic fire detectors when the system is in
'Manned' operating mode.
·
Limits the time for investigating the fire location to an individually pre-programmed period.
·
But if this time passes without resetting, the alarm is transmitted to the fire brigade.
·
The time remaining is shown on the display in minutes and seconds.
·
In the event of minor incidents, the alarm must be reset before V2 expires to prevent an un-
wanted remote alarm transmission.