Operating instructions
Œ•Ž
56
Building Technologies
A6V10225450_b_en_--
Fire Safety
2017.09.07
Activating / deactivating ZONE
What is this?
Zones can be activated manually from the AlgoRex terminal.
Which zones
can be activat-
ed?
The following zones can be activated, but with different impacts:
·
Detector zones
·
Control groups
How does this
impact on the
zones?
The activation/deactivation commands have the following impacts:
Element type
Impact
Detector zone
Activation produces a virtual alarm condition.
The danger level increases with each activation (depending on zone
type):
Warning
à
1st alarm
à
1st subsequent alarm
à
2nd subsequent alarm
Control groups
Activate/deactivate
Operating ac-
cess
If you still don't have operating access when starting operation work, the release procedure is
automatically called up.
Activating
a
detector zone
Perform the following steps to activate a detector zone:
Step
Action
Result / Comment
1
Navigate
to the DETECTOR ZONE
you want using:
<Operate..>
t
<Browse..>
t
<Browse FIRE DETECTION..>
- or -
<Browse EXTINGUISHING..>
t
<Select SECTION
¯
>
t
<Select ZONE
¯
>
The zone functions are displayed
2
Press
softkey
<ACTIVATE zone>
Implementation messages
'
Implementing ...
'
- and -
'
Implemented
'
- and -
Message depending on danger lev-
el (see above)
3
Repeat
step 2
until you reach the danger level re-
quired/you want