Operating instructions
Œ•Ž
69
Building Technologies
A6V10225450_b_en_--
Fire Safety
2017.09.07
REPLACING Sinteso
TM
DEVICE,
continued
Test condition -
> Off operating
mode
The command is available at zone level. This command switches the detector zone back to
normal operation. The message on the 'Detector zone/test condition' terminal goes out.
Perform the following steps to set a replaced Sinteso
TM
detector to 'Normal operation' operating
mode:
Step
Action
Result / Comment
1
Press
softkey
<Functions for sel. message..>
2
Press
softkey
<TEST/RENOVATION/INST.TEST
funct..>
3
Press
softkey
<Zone –> TEST OFF >
Implementation messages
'
implementing ...
'
NOTE
·
The corresponding zone has been reset to 'Normal operation'.
·
The message
Change in hardware configuration
disappears as soon as the service engi-
neer has transferred the modified data by uploading to AlgoWorks.
·
The replaced device is still fully functional.