Operating instructions
Œ•Ž
71
Building Technologies
A6V10225450_b_en_--
Fire Safety
2017.09.07
continued
Procedure
Perform the following steps to localize an open line:
Step
A results
1st pass
A results
2nd pass
1
Press
button
<Faults>
Press
button
<Isolation>
2
Select
the
Open line
message using the
scroll keys on the display
Select
the
Stub line forward
message using
the scroll keys on the display
3
Press
softkey
<Functions for sel. message..>
Press
softkey
<Functions for sel. message..>
4
Press
softkey
<More functions..>
Press
softkey
<More functions..>
5
Press
softkey
<More functions..>
Press
softkey
<More functions..>
6
Press
softkey
<Stub line forward>
Press
softkey
<Stub line backward>
7
Press
button
<
Õ
>
Press
button
<
Õ
>
8
Press
button
<Faults>
Press
button
<Faults>
9
Fault messages for all detectors af-
ter the open line are output
Fault messages for all detectors be-
fore the open line are output
The open line is between the detectors output in the 1st and 2nd passage.