Operating instructions
Œ•Ž
52
Building Technologies
A6V10225450_b_en_--
Fire Safety
2017.09.07
continued
Resetting
all
detector
zones
within one -
SECTION to
'Normal
operation' oper-
ating mode
Perform the following steps to reset
all
detector zones to 'Normal operation' operating mode:
Step
Action
Result / Comment
1
Press
button
<Information>
2
Select one of the detector zones to
be reset to 'Normal operation'
Use the scroll keys on the display
3
Press
softkey
<Functions for sel. message..>
F
See note below
4
Press
softkey
<Select SECTION
-
>
5
Press
softkey
<DETECTOR zone functions..>
6
Press
softkey
<All DETECTOR zones
-> INST. TEST OFF>
Implementation messages
'
Implementing ...
'
- and -
'
Implemented
'
NOTE
A summary section message is displayed under the following conditions:
·
When the section only contains zones of the same type.
·
When all these zones are in the 'Installation test' status.
If this collective message is present, it can be used to reset all the section's zones to normal op-
eration (via
<Functions for sel. message..>
).