Basic system information
&
108
Building Technologies
A6V10225450_b_en_--
Fire Safety
2017.09.07
continued
Acknowledging
alarm(s)
Switches from 'not acknowledged' to 'acknowledged'
Acknowledge
”
'Acknowledge' LED
flashes. This LED shows that acknowl-
edgement is possible.
Acknowledgement is undertaken by pressing the relevant
<Acknowledge> key
. Acknowledgement results in:
·
Buzzer stops sounding
·
Internal horn stops sounding
·
CAK V1 is stopped
·
CAK V2 is started
·
Reset is approved
·
Controls which depend on the 'not acknowledged' status, are
reset
A message appears on the display while the system is undertak-
ing the acknowledgement.
Resetting
alarm(s)
Resetting returns the system to standby.
Reset
•
Pressing the
<Reset> button
results in:
·
External horn stops sounding
·
CAK is reset
·
Controls which depend on the 'acknowledged' and 'active' sta-
tus, are reset
A message appears on the display while the system is resetting.
Handling alarms
which cannot be
reset
·
If zone alarm messages cannot be reset, a dialog to this effect appears and can be used to
directly switch off all the zones affected.
·
This dialog only appears if the number of zone alarm messages which cannot be reset does
NOT exceed a particular number.
·
This number of alarm messages can be programmed by the service engineer.