Basic system information
&
104
Building Technologies
A6V10225450_b_en_--
Fire Safety
2017.09.07
Message categories
Overview of message categories
Introduction
A distinction is made between a message's type and importance. They are split into categories
accordingly.
Message
categories
A distinction is made between the following message categories:
Category
Properties
Priority
·
Alarm
Danger messages recognized by the system
1
·
Fault
Messages which require a direct response
2
·
Isolation
System parts which are temporarily switched off
3
·
Information
Messages which do not require a direct response
4
Representation
on the
terminal
Faults
Information
Alarms
1
2
3
4
Alarms
category
Faults
category
Isolation
category
Information
category
If there is a message, the LED for this category lights up.
Properties
The table below shows the properties for the various messages.
Alarm
Fault
Isolation
Information
·
How are the
messages
displayed?
All messages
are displayed
spontaneous-
ly
All messages
are displayed
spontaneous-
ly
All messages
are displayed
spontaneously
Some messages are
displayed spontane-
ously (only certain
note messages, e.g.
warnings)
·
Under what
conditions?
Always
If there are no
alarm
messages
If there are no
messages of a
higher priority
If there are no mes-
sages of a higher pri-
ority
·
Overwrites
Messages
from all other
categories
Fault &
note messag-
es
Note messages
Never