Operating instructions
Œ•Ž
68
Building Technologies
A6V10225450_b_en_--
Fire Safety
2017.09.07
REPLACING Sinteso
TM
DEVICE
Simple replace-
ment process
for Sinteso
TM
devices
The process of replacing Sinteso
TM
devices is a simple one. Once the defective device has been
found, it can be replaced by a new device of the
same type
.
Operating ac-
cess
If you still don't have operating access when starting operation work, the release procedure is
automatically called up.
Test condition -
> On operating
mode
The command is available at zone level. A message to this effective is displayed on the termi-
nal. Only one element can be replaced per replacement session.
Perform the following steps to set a defective Sinteso
TM
detector to 'Test condition' operating
mode:
Step
Action
Result / Comment
1
Press
softkey
<Functions for sel. message..>
2
Press
softkey
<Select ZONE>
Implementation messages
'
implementing ...
'
3
Press
softkey
<TEST/RENOVATION/INST.TEST
funct..>
4
Press
softkey
<Zone ->TEST>
Implementation messages
'
implementing ...
'
NOTE
·
The corresponding zone is switched to 'Test'.
·
Replace defective device with one of the
same type
in the FDnet.
·
The AI in the device flashes for a few seconds (only if the device type is the same).
·
Once this command has been executed, the message
Change in hardware configuration
appears.
·
Once the test condition has been completed, the zone must be reset to normal operation us-
ing the 'Zone -> Test condition off' command, as described on the next page.