Operating instructions
Œ•Ž
33
Building Technologies
A6V10225450_b_en_--
Fire Safety
2017.09.07
Switching ALL ZONES in a SECTION OFF/ON,
continued
Switching ON
all
zones in a
section
You can use this command to switch ON all the detectors in a section. Perform the following
steps:
Step
Action
Result / Comment
1
Press
button
<Isolation>
Isolation messages are displayed
2
Use the scroll keys on the display to
select
Select section messages
(section in which all zones are to be
switched ON)
The section selected has a dark
background.
NOTE:
This section message only exists if all
zones in this section are switched
OFF.
3
Press
softkey
<Functions for sel. message..>
4
Press
softkey
<DETECTOR zone functions..>
The sub-menu is displayed.
5
Press
softkey
<All DETECTOR zones -> ON>
Implementation messages
'
Implementing ...
' - and -
'
Implemented
'
NOTE:
Perform the following steps if not all the zones in the section in question have been switched
OFF:
Step
Action
Result / Comment
1
Press
button
<Isolation>
Isolation messages are displayed
2
Use the scroll keys on the display to
select
one of the detector zones to
switch ON
The zone selected is displayed in-
versely
3
Press
softkey
<Functions for sel. message..>
4
Press
softkey
<Select SECTION
-
>
The SECTIONS menu is displayed
5
Press
softkey
<DETECTOR zone functions..>
The sub-menu is displayed.
6
Press
softkey
<DETECTOR zones
ON/OFF functions..>
The sub-menu is displayed.
7
Press
softkey
<All DETECTOR zones -> ON>
Implementation messages
'
Implementing ...
' - and -
'
Implemented
'