Operating instructions
Œ•Ž
30
Building Technologies
A6V10225450_b_en_--
Fire Safety
2017.09.07
Switching INDIVIDUAL ZONE OFF/ON (with time limit)
i
F
For general information about switching zones off/on, see chapter
"Switching INDIVIDUAL ZONE OFF/ON" on page 28.
Operating ac-
cess
If you still don't have operating access when starting operation work, the release procedure is
automatically called up.
Switching OFF
an individual
zone
with time
limit
The time for which the zone remains off can be limited. After this time, the zone is automatically
switched back on.
Perform the following steps to switch a zone OFF with a time limit:
Step
Action
Result / Comment
1
Press
softkey
<Operate..>
The main menu appears on the display.
2
Press
softkey
<Browse..>
The sub-menu is displayed.
3
Press
softkey
<Browse
FIRE DETECTION..>
The AREAS menu is displayed
Use the scroll keys to select the area you
want.
4
Press
softkey
<Select SECTION
¯
>
The SECTIONS menu is displayed
Use the scroll keys to select the section
you want.
5
Press
softkey
<Selected ZONE
¯
>
The ZONES menu is displayed
Use the scroll keys to select the zone you
want.
6
Press
softkey
<Zone -> OFF>
The sub-menu and the time input dialog
appear on the display.
7
Enter time
'hh:mm'
using numerical keys
·
The cursor indicates where the value is
to be entered.
·
The cursor moves as you enter the
numbers for hh:mm.
·
The maximum time limit is 18:00 hours.
8
Press
softkey
<OFF with time limit>
to complete the input
Implementation messages
'
Implementing ...
'
- and -
'
Implemented
'