Time and timekeeping
9410 series
network is required to implement a GPS scheme. For IRIG-B, one of your meter’s
digital inputs must be connected to the IRIG-B network, and the digital input must
be configured for IRIG-B time synchronization in addition to configuring your
meter’s clock.
NOTE:
Use the digital inputs located on the meter base for IRIG-B time
synchronization and other high-accuracy applications.
•
GPS over serial: A GPS receiver can synchronize the time of a meter up to ± 1 ms
of Coordinated Universal Time (UTC). For GPS over serial, your meter’s serial port
must be connected to a GPS receiver, and the serial port communications must be
configured with the correct protocol setting.
•
Network Time Protocol (NTP): NTP can typically synchronize the time of a meter to
± 10 to 100 ms, depending on network configuration. To implement NTP time
synchronization, your meter must be connected to an Ethernet network that has an
active NTP server and be configured with the server’s information.
Configuring time information using your meter’s display
Use the meter’s display to configure a variety of time parameters.
1. Go to
Setup Menu > Date/Time/Clock Setup > Date & Time Setup
.
2. Configure your time and date formats, time zone offset, and daylight savings time
offset. Press the down button to access the
Clock Setup
screen.
3. Configure the clock and time synchronization source, and the time synchronization
time format.
Date/Time/Clock setup
You can configure your meter’s date, time and clock parameters using the display.
Date & time setup
Parameter
Values
Description
Time Format
12 H, 24 H
Specifies how the time is displayed
Date Format
MM/DD/YYYY, DD/MM/
YYYY, YYYY/MM/DD
Specifies how the date is displayed
TZ Offset
-12:00:00 to 12:00:00
Sets the time zone of the meter’s location, relative
to UTC
DST Offset
-3:00:00 to 3:00:00
Sets the daylight savings time offset of the meter’s
location
Clock setup
Parameter
Values
Description
Clock Source
Internal, Line Freq, COMM
Specifies the time synchronization source
Time Sync Source
COM1, Ethernet,
Ethernet - ION, Ethernet -
DNP, IRIG-B
Specifies the port to receive time synchronization
signals
Time Sync Type
UTC, Local
Specifies whether time synchronization signals are
received in local time or UTC