Communications
9410 series
NOTE:
Your meter can have only one IEC 61850 configuration (CID) file loaded onto
its internal FTP storage. If additional CID files are loaded, IEC 61850 functions are
deactivated until the additional files are removed.
You can load the IEC 61850 configuration file and configure the IEC 61850 custom
modules using ION Setup.
Related Topics
•
FTP
•
Specifications
Loading an IEC 61850 configuration file using ION Setup
You can load an IEC 61850 configuration (CID) file using ION Setup over an Ethernet
connection.
You must have:
•
The IEC 68150 configuration file stored in a location accessible by ION Setup. The
configuration file is created by customizing the IEC 61850 device (ICD) file, which
can be downloaded from www.usa.siemens.com/pds.
•
FTP access to your meter from the computer running ION Setup.
NOTE:
Your meter can have only one IEC 61850 configuration (CID) file loaded onto
its internal FTP site. If additional CID files are loaded, IEC 61850 functions are
deactivated until the additional files are removed.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to
Communications > 3rd Party Protocols
and select the
IEC 61850
tab.
4. Highlight a parameter and click
Upload
. Navigate to where you stored your meter’s
CID file, select the file, and click
Open
.
Your meter reviews the CID file to determine if it is valid. This process may take
several minutes.
The CID status indicates whether the meter has received and validated an IEC
61850 CID file and is operating as an IEC 61850 server.
Configuring additional data for IEC 61850 using ION Setup
You can map additional data to IEC 61850 using ION Setup.
You must have a valid IEC 61850 configuration file loaded onto your meter for IEC
61850 functionality, but it is not necessary for configuring additional data.
NOTE:
You can configure additional data at any time, whether or not IEC 61850 is
operating on your meter.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to
Communications > 3rd Party Protocols
and select the
IEC 61850
tab.
4. Select the information type that corresponds to the type of meter information that
you want to add to your IEC 61850 data. Select analog for numeric information and
digital for boolean or binary information. Click
Edit
. The custom configuration
screen is displayed.
7EN05-0336-01
73