9410 series
Meter display
Related Topics
•
Revenue locking
Alarm icon
The alarm icon indicates the highest level and state of alarms detected by your meter.
For example, if the meter detects a low priority and a high priority active alarm, the
alarm icon indicates a high priority active alarm.
NOTE:
Alarms can only be viewed and acknowledged through your meter’s display.
Icon
Description
Active alarm indicator:
•
Red: high priority alarm state detected
•
Yellow: medium priority alarm state detected
•
Blue: low priority alarm state detected
The alarm indicator flashes until you acknowledge the alarm.
The alarm indicator changes to the historic alarm indicator of the appropriate level
when the alarm state is no longer detected by the meter.
NOTE:
Your meter’s display backlight flashes for unacknowledged high priority
active alarms.
Unacknowledged historic alarm indicator:
•
Red: unacknowledged high priority historic alarm
•
Yellow: unacknowledged medium priority historic alarm
NOTE:
Low priority historical alarms are not indicated.
The active alarm indicator changes to the historic alarm indicator of the appropriate
level when the alarm state is no longer detected by the meter.
No active or unacknowledged high or medium priority historic alarms
Related Topics
•
Alarms overview
Alarm and status LED indicators
Your meter has alarm and status LEDs on the display.
These LEDs cannot be configured for other uses.
LED
Description
Status
Off: unpowered
Steady green: normal operation
Flashing red: no communications (remote display only)
Steady red: firmware upgrade required (remote display only)
Flashing red/green: startup or firmware upgrade sequence in progress
Alarm
Off: no active or unacknowledged historic alarms
On: acknowledged active alarm
Flashing: active alarm
NOTE:
Your meter’s display backlight flashes for unacknowledged high priority
active alarms.