9410 series
Communications
3. Configure your meter’s SNMP parameters by selecting the parameter value.
Parameter
Range
Description
Enable SNMP .
Yes/no
Enables or disables SNMP on your meter.
SNMP Port Number
161 (default)
Enter your meter’s SNMP port number.
System contact
—
Enter the name of your SNMP system administrator.
System name
—
Enter a descriptive name for your meter.
System location
—
Enter your meter’s location.
Read-only Community Name
—
Enter the community string used for SNMP get (read-only) requests.
Read-write Community Name
—
Enter the community string used for SNMP set (read/write) requests. NOTE:
You can use the read/write community string for SNMP get (read-only)
requests.
Enable SNMP Traps
Enable/disable
Enables or disables SNMP trapping on your meter.
Enable High Priority Alarms
Yes/no
Enables trapping of events that create high priority alarms.
Enable Med Priority Alarms
Yes/no
Enables trapping of events that create medium priority alarms.
Enable Low Priority Alarms
Yes/no
Enables trapping of events that create low priority alarms.
Report Buffer Size
1 - 30
Enter the maximum number of trap messages to be stored before the trap
messages are sent. Traps are sent when the number of trap messages is
equal to or greater than this value.
Report Hold Time
1 - 300 seconds
Enter the maximum duration for trap messages to be held. Trap messages
are sent when the time after a trap event has occurred is equal to or greater
than this value.
Trap Rcvr1 Addr -
Trap Rcvr4 Addr
—
Enter up to four trap receiver IP addresses, where trap messages will be
sent.
4. Click
Apply
to configure the meter’s SNMP parameters.
IEC 61850
IEC 68150 is an Ethernet-based protocol designed for electrical substations.
It is a standardized method of communications, developed to support integrated
systems composed of multi-vendor, self-describing IEDs (intelligent electronic devices)
that are networked together.
Your meter can be integrated into an IEC 61850 system as an IED (or server)
supporting concurrent IEC 61850 client connections and an FTP connection (used for
transferring data or configuration files).
You can go to the IEC (International Electrotechnical Commission) website at www.iec.
ch for information about the IEC 61850 protocol. For more information on how IEC
61850 is implemented on your meter, see the
IEC 61850 and ION Technology
protocol
document.
IEC 61850 implementation
Your meter comes configured with a default set of meter data available to IEC 61850.
This default set of meter data is used in the default data sets and reports in the ICD file
(s) available for download from www.usa.siemens.com/pds.
NOTE:
Select the ICD file that matches your meter’s option module configuration.
You must load a valid IEC 61850 configuration (CID) file into the meter’s internal FTP
site in order to activate the IEC 61850 features of your meter.