Inputs / outputs
9410 series
Configuring option module digital inputs using ION Setup
You can configure option module digital inputs using ION Setup.
Digital inputs are available on your meter. You can add more digital inputs using
optional I/O modules.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to
Expansion Module > Option I/O Modules
and select the module tab
that corresponds to the option module with the digital input you want to configure.
4. Select the digital input channel and click
Edit
.
The setup screen for that digital input is displayed.
5. Configure the digital input by selecting the parameter and clicking
Edit
.
6. Once the parameter has been configured, click
OK
to save the setting to the meter.
Parameter
Value/Range
Description
Input Mode
Pulse, KYZ, A/C,
IRIG-B
1
Specifies how the meter processes the signal:
•
Pulse: the meter counts an entire pulse (from off-on to
on-off) as one input.
•
KYZ: the meter counts a transition (from off-on or from
on-off) as one input.
•
A/C: the meter detects analog signals where the ON
condition is based on the presence of an AC signal.
•
IRIG-B
1
: the meter detects an IRIG-B time
synchronization signal.
Polarity
Inverting/Non-
Inverting
Specifies if the signal from the digital port is inverted or not
inverted.
Debounce
0.000 - 1.000
Specifies how long (in seconds) the signal must remain in a
state to be considered a valid state change.
Port
Defined by your
meter’s hardware
Your meter’s physical digital input port.
1
IRIG-B can only be connected to one of the digital inputs located on the meter base, not an option
module.
WAGES monitoring
WAGES monitoring allows you to record and analyze all energy sources and utilities
usage.
Your energy system may use several different types of energy. For example, you may
consume steam or compressed air for industrial processes, electricity for lights and
computers, water for cooling and natural gas for heating. WAGES monitoring collects
the usage information from all these different energy sources to enable a more
complete energy analysis.
WAGES information can help you:
•
Identify losses or inefficiencies.
•
Modify demand to reduce costs.
•
Optimize energy source usage.
WAGES example
This example shows WAGES monitoring for a water flow meter.
You can connect your meter’s digital input to a transducer that sends a pulse for every
15 kiloliters (4000 US Gal) of water. After configuring an input metering channel and