9410 series
Alarms and alerts
Default alarms
Your meter comes with default alarms.
NOTE:
Some alarms require configuration in order to operate.
Name
Priority
Description
Current Sag Ph1 - 3
High
Current sag alarms for phase 1, 2, 3
Current Swell Ph1 - 3
High
Current swell alarms for phase 1, 2, 3
Sag/Swell
High
Voltage sag/swell alarm
Over I unbal
Medium
Over unbalanced current alarm
Over V unbal
Medium
Over unbalanced voltage alarm
Over THD V1 - 3
Medium
Over total harmonic distortion (THD) voltage alarms
Over kW (P) sd
Medium
Over kW sliding demand alarm
Over I a - c, (1 -3) 4
Medium
Over current alarms
V1 - V3 Setpoint
Medium
Voltage setpoint alarms
Freq Setpoint
Medium
Frequency setpoint alarm
4-30 Volt Intrp Ph1 - 3
Low
4-30 voltage interruption power quality alarms
Digital In
Info Only
Digital input alarms
Number of alarms determined by the total number of available digital inputs
NOTE:
These alarms are not displayed by default.
Alarm information
You can view information about an alarm from your meter’s display.
Only alarms with a priority of low, medium or high are displayed.
Parameter
Description
Alarm
The name of the alarm (for example, Over THD V1).
Priority
Low, medium or high alarm priority.
Date
The date and time the alarm was triggered.
Duration
The duration of the alarm (only applies to inactive alarms).
Ack
The date and time when the alarm was acknowledged (only applies to
acknowledged alarms).
Value
Active alarm: The maximum value detected when the alarm was triggered.
Historic alarm: The maximum value detected during the duration of the alarm.
Viewing and acknowledging alarms using the meter’s display
You can view and acknowledge alarms using your meter’s display
1. Press the home button to display your meter’s data screen menu.
2. Navigate to
Alarms > Active Alarms
to view and acknowledge active alarms, or
navigate to
Alarms > Historic Alarms
to view and acknowledge alarms that are no
longer active.
130
7EN05-0336-01