9410 series
Communications
DNS setup
Parameter
Values
Description
Primary DNS
As defined by your network’s
system administrator
Sets the address for the primary DNS server that is
configured to resolve domain names
Secondary DNS
As defined by your network’s
system administrator
Sets the address for the secondary DNS server
that is configured to resolve domain names
COM1 setup
Parameter
Values
Description
Protocol
ION, Modbus RTU, Modbus
Master, DNP v3.00,
EtherGate, GPS: Truetime/
Datum, GPS: Arbiter, GPS:
Arbiter-Vorne, Factory
Sets the communications protocol for your meter’s
RS-485 port
Baud Rate
2400, 4800, 9600, 19200,
38400, 57600, 115200
Sets the data rate, in bits per second
RTS Delay
0 to 1
Sets the transmit delay in seconds
Unit ID
1 to 9999
Sets the meter’s unique ID on the RS-485 network
NOTE:
Modbus serial device range 0 to 247
Serial Port
8N1, 8N2, 8E1, 8E2, 8O1,
8O2
Sets the parity and stop bits for the port
RS485 Bias
Off, On
Turns on biasing when mastering devices over the
RS-485 port
NTP Address
Parameter
Values
Description
NTP Server
As defined by your network’s
system administrator
Specifies the IP address of the SNTP or NTP
server used by the meter for time synchronization
SMTP Address
Parameter
Values
Description
SMTP Server
As defined by your network’s
system administrator
Specifies the IP address of the SMTP server used
by the meter for sending email
ION
ION is the native protocol and architecture of your meter.
The basic building blocks of ION architecture are the ION modules, each of which is
specialized to perform a specific task and contains data and instructions on how to
manage that data. ION modules are combined (linked) together to create the meter’s
functions and features. ION modules that are linked together to perform a specialized
task are called a framework, such as the Power Quality framework. These different
functional frameworks are then grouped together to define the entire meter, and are
collectively referred to as the device template.
Your meter ships with a default device template which provides extensive capabilities.
You can also configure your meter’s template to modify your meter’s existing functions
or to create new functions.