Communications
9410 series
NOTE:
The number of events or maximum time delay settings only apply to enterprise
SNMP traps.
See the ION Reference, available from www.usa.siemens.com/pds, for detailed
information on the SNMP Mapping, SNMP Options and Alarm Options modules.
Related Topics
•
Configuring SNMP using ION Setup
•
Configuring SNMP using your meter’s webpages
Default SNMP mapping
Enabling SNMP provides SNMP access to the meter values linked to the SNMP
Mapping module.
You can configure the SNMP Mapping module to link to different meter values. By
default, the following meter values are linked to the SNMP Mapping module:
I a
kVAR tot
Vll ca
Vln avg
Ib mean
kW sd mx del-
rec
I b
kVA tot
Vll avg
Freq
Ic mx
kW sd del
I c
PF sign tot
Vln a
Ia mx
Ic mean
kW sd rec
I avg
Vll ab
Vln b
Ia mean
kW sd mx del
kW sd del-rec
kW tot
Vll bc
Vln c
Ib mx
kW sd mx rec
kVAR sd mx
del
kVAR sd mx
rec
kVAR sd mx
del-rec
kVAR sd del
kVAR sd rec
kVAR sd del-
rec
kVA sd mx del
kVA sd mx rec
kVA sd mx del-
rec
kVA sd del
kVA sd rec
kVA sd del-rec
kWh del
kWh rec
kWh del-rec
kVARh del
kVARh rec
kVARh del-rec
kVAh del
kVAh rec
kVAh del-rec
The following meter information is always provided by default and cannot be
configured:
Voltsmode
Model number
Serial number
Device name
Firmware version
MIB version
If you change your meter’s default values you must modify the custom MIB file to
reflect the new values.
Changing your meter’s default SNMP configuration assumes that you have an
advanced understanding of ION architecture, SNMP, and the communications network
and power system that your meter is connected to.
See the ION Reference, available from www.usa.siemens.com/pds, for detailed
information on the SNMP Mapping module.
Configuring your SNMP MIB file
You must configure your MIB file if you have modified the default SNMP information
provided by the meter in order for the MIB file labels to reflect the modified values.
Download the ION MIB file from www.usa.siemens.com/pds.