Communications
9410 series
NOTICE
DATA LOSS
Failure to follow these instructions can result in equipment damage.
Record your device's user and password information in a secure location.
1. Start ION Setup.
2. Open the
Setup Assistant
for your device.
3. Select
Communications
>
Network Settings
and click the
TCP/IP
tab.
4. Select a setting and then click
Edit
. Configure the settings (for example, IP
address, subnet or gateway) to match your communications system.
Parameter
Value
Description
Ethernet device name
configurable
This name is associated with
your meter when using DPWS.
By default, it is the meter type
and the last 6 characters of its
MAC address.
Enable IPv6
Yes/no
Specifies if IPv6 is enabled or
disabled.
IP address
Contact your local network
administrator for parameter
values.
The Internet protocol address
of your device.
SubnetMask
The Ethernet IP subnetwork
address of your network.
Gateway
The Ethernet IP gateway
address of your network.
Rx timeout
configurable
Specifies the number of
seconds the meter waits for
communication
acknowledgments.
Modbus TCP Idle Timeout
configurable
Specify number of seconds the
meter waits before
disconnecting an idle Modbus
TCP connection.
Modbus Gateway
Disabled/COM1
Specify the port on which
Modbus Gateway sends/
receives Modbus TCP
requests.
NOTE:
For Modbus gateway to
function properly, the serial port
protocol must be set to Modbus
Master.
MAC address
Read-only
The media access control
(MAC) address is factory set
and is for reference only.
5. Click the
Protocols
tab.
6. Select a protocol and then click
Edit
. Select whether the protocol connection
requests are accepted by the meter, and configure the port number. Existing
connections are not affected, but any new connections must comply with the
meter’s latest settings.
NOTE:
The protocol port number is not configurable on all protocols.