Measurements

9410 series

Power demand

Power demand is a measure of average power consumption over a fixed time interval.

NOTE:

If not specified, references to “demand” are assumed to mean “power

demand.”

The meter measures instantaneous consumption and can calculate demand using
various methods.

Peak demand

Peak (or maximum) demand is the highest demand level recorded over the billing
period.

Power utilities generally bill commercial customers based on their peak usage levels,
called peak demand (in kW) and energy consumption (in kWh). Peak (or maximum)
demand is the highest demand level recorded over the billing period. You can view
peak demand values on your meter’s display.

Your meter calculates the average current demand and kW, kVAR and kVA demand
using sliding window demand methods. The meter supports coincident demand values
when a peak demand is detected.

Your meter’s default configuration is suitable for most applications, or you can
customize it for your specific application. You can configure the minimum time between
consecutive demand resets.

NOTE:

If not specified, references to “demand” are assumed to mean “power

demand”.

Peak demand reset lockout

The demand reset lockout time sets the minimum time allowed between consecutive
demand resets; the meter ignores any attempts to reset demand that occur within the
lockout period.

The peak demand reset lockout period is user-configurable, with a default value of 25
days.

See the ION Setup online help for instructions on how to configure demand peak and
the demand reset lockout period on your meter.

See the ION Reference, available from www.usa.siemens.com/pds, for detailed
information on how Sliding Window Demand modules measure and calculate demand
values.

Related Topics

Meter resets

Data viewing using your meter’s display

Sliding window demand

To calculate demand values, your meter uses the sliding window averaging (or rolling
interval) method which divides the demand interval into a set number of subintervals of
specified duration.

The demand is measured electronically based on the average load level over the most
recent set of subintervals. Sliding window demand also provides predicted demand
values.

7EN05-0336-01

143

Содержание 9410DC

Страница 1: ...9410 series User manual 7EN05 0336 01 09 2015 www usa siemens com pds ...

Страница 2: ...ollow this symbol to avoid possible injury or death DANGER DANGER indicates a haz ardous situation which if not avoided will result in death or serious injury WARNING WARNING indicates a ha zardous situation which if not avoided could result in death or serious injury CAUTION CAUTION indicates a haz ardous situation which if not avoided could result in minor or moderate injury NOTICE NOTICE is use...

Страница 3: ...rity to operate the equipment This digital apparatus complies with CAN ICES 3 B NMB 3 B About this manual This manual discusses features of the 9410 series power meter and provides installation and configuration instructions Throughout the manual the term meter refers to all models of the 9410 All differences between the models such as a feature specific to one model are indicated with the appropr...

Страница 4: ...9410 series 4 7EN05 0336 01 ...

Страница 5: ...p 17 Current polarity setup 17 Nominal values 17 Minimum configuration requirements for basic metering 17 Lost user access 17 Hardware reference 18 Supplemental information 18 Meter base 18 Panel meter 18 DIN meter 19 Remote meter display RMD 19 Mounting adaptors 20 Terminal covers 20 Replacement hardware 20 LED locations 20 Energy pulsing LED behavior 21 Revenue lock LED behavior 21 Remote displa...

Страница 6: ... standard security using ION Setup 42 Configuring users and passwords using ION Setup advanced security only 44 Loading an existing security configuration file scf using ION Setup 45 Communications 46 Communications overview 46 Configuring communications using the display 46 Ethernet 46 Serial 50 ION 52 Modbus 53 Key terms 53 Ethernet gateway 62 FTP 65 SNMP 66 IEC 61850 72 COMTRADE 75 DNP 76 Time ...

Страница 7: ...y terms 107 Setpoint learning overview 109 Learning installation mode and learning duration 110 Inputs outputs 112 I O Overview 112 Input output ION modules 112 Input output ION modules ports and labels 112 I O option modules 113 Analog inputs 114 Analog outputs 116 Digital inputs 118 IRIG B time synchronization 118 WAGES monitoring 119 Input metering 120 Digital outputs 122 Energy pulsing 124 Ala...

Страница 8: ...54 Accuracy test requirements 154 Signal and power source 154 Control equipment 154 Environment 154 Reference device or energy standard 155 Energy pulsing 155 Verifying accuracy test meter settings 155 Verifying accuracy test 156 Calculate the number of required pulses 157 Percentage error calculation for accuracy verification testing 158 Typical sources of test errors 158 Accuracy verification te...

Страница 9: ...eat communications and I O wiring connected to multiple devices as hazardous live until determined otherwise Do not exceed the device s ratings for maximum limits Never short the secondary of a potential voltage transformer PT VT Never open circuit a current transformer CT Always use grounded external CTs for current inputs Do not use the data from the meter to confirm power is off Replace all dev...

Страница 10: ... port Ethernet two physical ports one Ethernet IP address Water Air Gas Electricity Steam WAGES support Time of use support Trending and forecasting Alarms active and historic display viewing and acknowledgment Multiple languages supported Your meter in an energy management system In an energy management system the 9410 meter collects and aggregates data This data is used to perform non critical c...

Страница 11: ...Volt squared hours and amp squared hours Energy parameters can be logged automatically on a programmed schedule All energy values represent the total for all three phases Demand Your meter supports several demand calculation methods including block rolling block synchronized and predicted demand It can measure demand on any instantaneous value and record peak maximum and minimum demand with time a...

Страница 12: ...and kVA Power factor Frequency Voltage unbalance Plus any measured value Power quality Your meter measures and records voltage and current sags and swells Your meter also has many power quality related features Disturbance direction detection this allows the meter to analyze disturbance sag swell information to help determine the direction of the disturbance relative to the meter Setpoint learning...

Страница 13: ...ion Depending on the priority of the alarm your meter s display also flashes You can view and acknowledge active alarms and historic alarms and events through the display and software webpages An active alarm becomes a historic alarm when the alarm condition no longer exists Meter internal web server feature Your meter s internal web server provides quick and easy access to real time energy and ba...

Страница 14: ...line ION Setup help available from www usa siemens com pds for instructions on connecting to your meter Meter types The 9410 series is available in two physical form factors and has several accessories Model Commercial reference Description 9410DC US2 9410DC Panel mounted meter with integrated display 9410TC US2 9410TC DIN rail mounted meter without display which can be connected to a remote displ...

Страница 15: ...r models where sealable voltage and current covers are required to comply with revenue or regulatory standards The meter terminal covers must be installed by a qualified installer Refer to your meter s installation sheet or the instructions that came with your terminal covers for instructions on installing the terminal covers Replacement hardware You can order replacement mounting and installation...

Страница 16: ...guration PhaseOrder ABC ACB The power system s phase order PT CT setup Parameter Values Description PT Primary 1 to 999 999 99 The potential transformer s primary winding voltage rating NOTE PTs are also referred to as a VTs or voltage transformers PT Secondary 1 to 999 999 99 The potential transformer s secondary winding voltage rating NOTE PTs are also referred to as a VTs or voltage transformer...

Страница 17: ...e power system I Nominal 1 to 999 999 The nominal normal current of the power system Nominal Frequency 50 60 The nominal normal frequency of the power system Minimum configuration requirements for basic metering At a minimum you must configure some parameters to help your meter perform basic metering functions Setup screen Screen Minimum configuration Meter Setup Volts Mode Volts mode PT CT Setup ...

Страница 18: ...ur product s catalog pages at www usa siemens com pds for information about your device its options and accessories You can download updated documentation from www usa siemens com pds or contact your local Siemens Industry representative for the latest information about your product Meter base Your meter base has two form factors panel mount and DIN mount Panel meter A Voltage inputs B Control pow...

Страница 19: ...s com pds or consult your local Siemens Industry representative for information about your device its options and accessories Remote meter display RMD The remote meter display can be used with DIN meters It has the same buttons and icons as the display on a panel meter and is powered by the connection to the meter A remote display cannot be used with meters that have an integrated display A D C B ...

Страница 20: ...r insulation The terminal covers are secured by tamper resistant meter seals These covers are included for meter models where sealable voltage and current covers are required to comply with revenue or regulatory standards The meter terminal covers must be installed by a qualified installer Refer to your meter s installation sheet or the instructions that came with your terminal covers for instruct...

Страница 21: ... is revenue locked Flashing New revenue lock state is pending power cycle your meter to set the revenue lock to on or off Remote display connection LED behavior There are two LEDs in the remote display connector that indicate the state of communications between the meter and remote display LED Description Green link On link established Off no link established with the remote display Check the conn...

Страница 22: ... voltage is greater than the specified direct connect maximum voltage you must use voltage potential transformers VTs PTs to step down the voltages RS 485 wiring Connect the devices on the RS 485 bus in a point to point configuration with the and terminals from one device connected to the corresponding and terminals on the next device RS 485 cable Use a shielded 2 twisted pair or 1 5 twisted pair ...

Страница 23: ...nnected to your meter without specialized equipment Option modules are identified based on the physical order of the attached modules The option module attached directly to the meter is module A the module attached to module A is module B and so on The option module identifier is added to the ION module name and ION label to uniquely describe each possible combination of option modules A Option mo...

Страница 24: ...hat can be attached is the physical strength of the meter mounting hardware If your meter is mounted in an area subject to vibration or other physical stresses your meter s ability to physically support multiple option modules and maintain a seal against the mounting surface may be affected Refer to Mechanical characteristics page 164 for more information NOTICE EQUIPMENT DAMAGE Failure to follow ...

Страница 25: ...period of inactivity When the meter detects an unacknowledged active high priority alarm the display flashes until the alarm is acknowledged Home button Pressing the home button takes you to the associated menu screen If you are in a data screen pressing the home button takes you to the display menu and pressing home twice takes you to the summary display screen If you are in a setup screen pressi...

Страница 26: ...cknowledged historic alarm indicator Red unacknowledged high priority historic alarm Yellow unacknowledged medium priority historic alarm NOTE Low priority historical alarms are not indicated The active alarm indicator changes to the historic alarm indicator of the appropriate level when the alarm state is no longer detected by the meter No active or unacknowledged high or medium priority historic...

Страница 27: ...ssing this button selects or confirms the highlighted value Cancel Pressing this button cancels the current selection and returns you to the previous screen Graphic Pressing this button takes you to a graphical data display Numeric Pressing this button takes you to a numeric data display Info Pressing this button takes you to a detailed information screen Edit Pressing this button allows you to ed...

Страница 28: ...ower T otal Max Power Power Sum mary Power Total Power Phase A Power Phase B Power Phase C Peak De mand Delivered Total TOU Peak Demand Delivered A B Dem and Total Demand Delivered Total Demand Received Peak De mand Received Total TOU Peak Demand Received A B Power F actor Total Min Power F actor Total Max TOU Peak Demand Delivered C D TOU Peak Demand Received C D Power F requency Compliance Power...

Страница 29: ...ion Nameplate MID meter only Feature set firmware version firmware CRC Pulse constant and template information Nameplate MID meter only Volts mode nominal voltage nominal current nominal frequency PT ratio and CT ratio Custom screens Custom screens Data viewing using your meter s display Use the navigation buttons to view data on your meter s display The following examples show how to use the navi...

Страница 30: ... Press or to highlight a specific alarm in this case a 4 30 voltage interruption alarm Press to display detailed information about the highlighted alarm Press both and simultaneously to acknowledge all historical alarms 5 Press to return to the menu Example viewing the voltage screens Use the display navigation buttons to view screens display detailed information and display graphical representati...

Страница 31: ...list of additional screens 3 Press or to highlight an additional screen in this case Volts II Average Press to go to the highlighted screen Volts II Average displays the average line to line voltage 4 Press to view a graphical display of average voltage values then press to return to the numeric display Press to return to Volts L L 7EN05 0336 01 31 ...

Страница 32: ...ter configuration can be performed through the display using the meter s webpages or through software This section contains information on how to set up the meter using the display You must have your meter s security settings configured to allow front panel display programming in order to set up the meter using the display NOTE Your display may appear differently than shown depending on your meter...

Страница 33: ... display may appear differently than those shown depending on your meter s power system and display and localization settings NOTE Your navigation icons change color depending on the type of screen being viewed If an icon is gray that navigation option is not available and nothing will happen when you press the button associated with that icon NOTE Your meter goes back to displaying data after a p...

Страница 34: ... the value of the highlighted digit 0 9 Press to go to the next digit Press to enter your password The Volts Mode configuration screen is displayed 5 Press or to highlight the desired volts mode from the list in this case 3W WYE Press to select the highlighted volts mode A confirmation screen is displayed showing your meter s previous setting and newly selected setting 6 Press to confirm and the n...

Страница 35: ...m the new value or to revert to the original value Related Topics Security overview Minimum configuration requirements for basic metering Display setup You can configure your meter s basic display parameters using the display Screen setup Parameter Values Description Backlight Timeout 0 to 720 Specifies how many seconds the display s backlight remains lit after the last button press Label symbol s...

Страница 36: ...ber of decimal places displayed for currents Power Resolution 1 1 X 1 XX 1 XXX 1 XXXX Specifies the number of decimal places displayed for power and energy measurements Language setup Select the language to be shown on the meter s display By default your meter has the following languages English Spanish French German Italian Portuguese Russian Chinese simplified Remote display troubleshooting icon...

Страница 37: ...istant for your meter 3 Navigate to Custom Displays 4 Select Custom Displays from the Front Panel tab and click Edit ION Setup loads your meter s display information into the Display Editor screen 5 Rename delete or change the order of custom displays through the Display Editor screen Click New to add a new display Click Edit to bring up the Display setup screen where you can configure new or exis...

Страница 38: ...elect your digit display properties Resolution Specifies the number of decimal places displayed Last Digit Enter the title to be shown at the top of your custom display 9 Click Send to save the changes in the meter 38 7EN05 0336 01 ...

Страница 39: ...u to enable or disable your meter s webpages Allow web server programming Standard advanced This option allows you to enable or disable the ability to configure your meter using the meter s webpages NOTE To enable Allow web server programming you must have active web server enabled Allow Modbus programming Advanced only This option can only be enabled in advanced security and is disabled for stand...

Страница 40: ...ked out However the invalid login attempt events are recorded if the meter access events are configured to record invalid access attempts Session timeout specifies the active duration for a protocol during this time repeated invalid login attempts using the same USER password combination are not registered repeated invalid attempts with different combinations are still registered Session timeout o...

Страница 41: ...at the user password you enter is compatible with the software used to communicate with your device Schedule regular changes to your meter s display and user passwords Record your meter s display and user passwords in a secure location If your meter s user access information is lost you must return the meter to the factory where your meter is reset to its factory defaults and all logged data is lo...

Страница 42: ...isplay NOTE This is also the password used to access the meter s webpages when standard security is enabled Changing your meter s display password using the display You can change your display password using your meter s display NOTE The display password is also used as the webpage password if standard security is enabled 1 Go to Setup Menu Password Setup 2 Configure your meter s display password ...

Страница 43: ...ity parameters as required some parameters can only be configured using advanced security Click Next to configure protocol access information The protocol lockout screen is displayed 6 In the protocol lockout screen select the protocols that you want to be protected by the protocol lockout function Select each protocol and click Edit to configure the protocol specific parameters 7 Enter the lockou...

Страница 44: ...ability to configure your device using the display Allow broadcasting time synchronization Advanced only This option can only be disabled in advanced security and is enabled for standard security Protocol specific security parameters available using ION Setup Parameter Values Description Protocol lockout 0 255 The number of invalid login attempts before access is denied If protocol lockout 0 there...

Страница 45: ...ead The user can view all parameters except the security configuration Peak demand reset The user can reset peak demand values Test mode The user can put the meter into test mode not applicable to all devices Full meter config The user can configure all aspects of the meter except demand resets test mode or security Security config The user can configure security Loading an existing security confi...

Страница 46: ...cations Setup IP Address Setup 2 Configure your meter s IP Address and other network information as required NOTE Your meter s default IP address is 169 254 0 10 3 Press the down button to access the next screen of meter communications settings and configure as required Ethernet Ethernet communications connections The meter supports a single IP address on both of its two physical Ethernet connecti...

Страница 47: ... your network system administrator before connecting the device to your local area network LAN After the meter s Ethernet port is configured and connected to the LAN you can use ION Setup to configure other meter setup parameters Protocols ports and connections The Ethernet protocols supported by your device allow simultaneous connections through the IP service ports Protocol Port default Number o...

Страница 48: ...our computer your meter automatically appears on the network By default the meter is named meter type _ last six digits of MAC address NOTE You do not need to configure your meter s IP address for self discovery over Ethernet an IPv6 address is automatically generated from your meter s MAC address and self discovery takes place over IPv6 Double clicking the meter s network icon takes you to the me...

Страница 49: ...ce SubnetMask The Ethernet IP subnetwork address of your network Gateway The Ethernet IP gateway address of your network Rx timeout configurable Specifies the number of seconds the meter waits for communication acknowledgments Modbus TCP Idle Timeout configurable Specify number of seconds the meter waits before disconnecting an idle Modbus TCP connection Modbus Gateway Disabled COM1 Specify the po...

Страница 50: ... the meter s display webpages or ION Setup to configure your meter s default RS 485 settings Your meter has one RS 485 connection Your meter must have a unique unit identifier address and have the following settings match the rest of the devices on the RS 485 bus Protocol Baud rate Parity and stop bits You can configure the following settings to help optimize communications performance RTS delay R...

Страница 51: ...teway using ION Setup Communications setup You can configure your meter s basic communications parameters using the display IP address setup Parameter Values Description IP Address As defined by your network s system administrator Sets the IP address for the meter NOTE Your meter s default IP address is 169 254 0 10 SubnetMask As defined by your network s system administrator Used if subnetting ap...

Страница 52: ...Address Parameter Values Description NTP Server As defined by your network s system administrator Specifies the IP address of the SNTP or NTP server used by the meter for time synchronization SMTP Address Parameter Values Description SMTP Server As defined by your network s system administrator Specifies the IP address of the SMTP server used by the meter for sending email ION ION is the native pr...

Страница 53: ...device Modbus master A device that issues commands and receives responses from Modbus slave devices Serial Modbus networks can only have one Modbus master per network Modbus RTU Serial Modbus protocol format Modbus RTU transmits data using binary Master and slave devices must use the same format Modbus register address Identifies the data to read write Modbus register maps are available for Modbus...

Страница 54: ...meter can function as a Modbus master with serial Modbus slave devices A Ethernet B Your meter C RS 485 Modbus RTU D Modbus slaves Your meter as a Modbus master with Ethernet Modbus slave devices Your meter can function as a Modbus master with Ethernet Modbus slave devices A Ethernet B Your meter C Modbus slaves Supported Modbus features Your meter supports specific Modbus data classes data format...

Страница 55: ...us masters support two versions of IEEE float with different word orders high low Big Endian low high Little Endian 16 bit data one word is transmitted with most significant byte first and least significant byte second 32 bit data two words is transmitted with the most significant word first and the least significant word second Modbus function codes Function Description Master slave 1 Read coil s...

Страница 56: ...not allowed for that register in the device The requested register is part of a multi word value Modbus invalid read registers responses Invalid type Read response Unmapped unused 1 register 0x8000 Reserved1 register responses by type Signed integer 16 bit 0x8000 Unsigned integer 16 bit 0xFFFF Signed integer 32 bits 0x80000000 Unsigned integer 32 bits 0xFFFFFFFF Signed integer 64 bits 0x8000000000...

Страница 57: ...n the serial Modbus network Stop bits and parity The communication stop bits and parity for example 8N1 must be the same for all devices on the serial Modbus network Unit ID Each device on the serial Modbus network must have a unique unit ID also called the device address Modbus best practices for Ethernet In order for your meter to operate as an Ethernet Modbus device you must complete some prere...

Страница 58: ...ies of Data Mapping modules which also determine the values shown on your device s display and webpages The Data Mapping modules are named based on the type of information they map to Modbus Data Mapping module Description Data Mapping Dmd Modules Maps kW kVA and kVAR demand data such as kW sd del sliding demand kilowatts delivered as well as current demand such as I a sd sliding demand phase A cu...

Страница 59: ...up and select the serial communications setup screen 2 Configure the serial port s Modbus parameters as required Parameter Setting Protocol Modbus RTU or Modbus master RS485 Bias Off if the meter is a Modbus slave On if the meter is a Modbus master 3 Configure the meter s other serial port parameters as required For Modbus master you must add the Modbus slave devices using ION Setup Related Topics...

Страница 60: ...rs and their start and end addresses 4 Select the map name and click Edit The Modbus Slave Mode Setup screen is displayed 5 Select your meter s method of Modbus slave mapping If you select Default or Disabled click Finish to configure your meter and return to the Setup Assistant otherwise select Next to access the Modbus Slave Map Setup screen Option Description Default Sets your meter to use the ...

Страница 61: ...ore configuring your meter as a Modbus master NOTE Devices supporting multiple simultaneous Modbus TCP connections can have communications delays Adjust your network timeout settings to accommodate this The meter as a Modbus master over TCP IP attempts to communicate with a slave device for up to 100 seconds as per the RFC1122 standard before moving on to the next slave device 1 Start ION Setup 2 ...

Страница 62: ...r TCP connections communicate through the gateway meter to a serial network of Modbus devices Related Topics Specifications EtherGate The meter can function as an Ethernet gateway EtherGate EtherGate is a protocol agnostic communications method that lets you communicate through a gateway meter to a serial network of devices letting ION or other RTU over TCP data pass through the gateway meter to o...

Страница 63: ...en forwards it to the addressed slave device This functionality allows the use of monitoring software to access information from slave devices for data collection trending alarm event management analysis and other functions Configuring EtherGate using the display Use the meter s display to configure a serial port to use the EtherGate protocol 1 Navigate to Setup Menu Communications Setup and go to...

Страница 64: ... same baud rate serial port settings for example 8N1 and protocol ION Confirm each serial device has a unique unit identifier Confirm the serial network of devices are connected to the gateway meter s serial communication port Confirm your gateway meter is communicating over Ethernet 1 Start ION Setup 2 Open the Setup Assistant for your meter 3 Navigate to Communications Serial settings and select...

Страница 65: ...and meter accessories File transfer protocol FTP is a standard client server network protocol used to transfer files over TCP Ethernet networks FTP memory allocation Your meter s FTP memory usage changes when you copy a file to the meter s internal FTP site or modify a feature that uses the meter s FTP site If you attempt to load a file onto your meter s FTP site that is too large your FTP program...

Страница 66: ...pending on your FTP software and meter security settings you may be prompted for login credentials NOTE With standard meter security no user configured enter login credentials of 9410 and the meter password to connect to the meter For advanced meter security enter a valid user and password 3 Navigate to the appropriate folder on your meter 4 Close your FTP software to disconnect from the meter The...

Страница 67: ...quely identifies and labels a managed object in the MIB Trap receiver An NMS that is configured to receive traps and whose IP address is an SNMP trap destination The meter in an SNMP system Your meter is a managed device with an SNMP agent in an SNMP network A Trap receiver s B SNMP agent meter C NMS with SNMP manager software and MIB file installed NOTE The NMS computer can also function as a tra...

Страница 68: ...MP system administrator System name enter a descriptive name for your meter System location enter a description of your meter s location SNMP trapping SNMP trapping allows your meter s agent to notify the NMS of events with an unsolicited SNMP message a trap of the meter s alarm event You can enter up to four IP addresses for SNMP trap notification for generic and enterprise specific traps For ent...

Страница 69: ...R sd mx del rec kVAR sd del kVAR sd rec kVAR sd del rec kVA sd mx del kVA sd mx rec kVA sd mx del rec kVA sd del kVA sd rec kVA sd del rec kWh del kWh rec kWh del rec kVARh del kVARh rec kVARh del rec kVAh del kVAh rec kVAh del rec The following meter information is always provided by default and cannot be configured Voltsmode Model number Serial number Device name Firmware version MIB version If ...

Страница 70: ...e and is now connected to voltage line toneutral phase C Original OID entry Vln_a OBJECT TYPE SYNTAX DisplayString SIZE 0 255 ACCESS read only STATUS mandatory DESCRIPTION Host Meter Voltage Line A to Neutral Units V Volts Siemens Industry 34 You must update the variable name and description to match the meter values connected to the SNMP Mapping module Value Original Updated Variable name Vin_a V...

Страница 71: ... Read write community Enter the community string used for SNMP set read write requests NOTE You can use the read write community string for SNMP get read only requests System contact Enter the name of your SNMP system administrator System name Enter a descriptive name for your meter System location Enter your meter s location 5 Review the rest of the SNMP information and modify if necessary Relate...

Страница 72: ...ges to be held Trap messages are sent when the time after a trap event has occurred is equal to or greater than this value Trap Rcvr1 Addr Trap Rcvr4 Addr Enter up to four trap receiver IP addresses where trap messages will be sent 4 Click Apply to configure the meter s SNMP parameters IEC 61850 IEC 68150 is an Ethernet based protocol designed for electrical substations It is a standardized method...

Страница 73: ...Setup Assistant for your meter 3 Navigate to Communications 3rd Party Protocols and select the IEC 61850 tab 4 Highlight a parameter and click Upload Navigate to where you stored your meter s CID file select the file and click Open Your meter reviews the CID file to determine if it is valid This process may take several minutes The CID status indicates whether the meter has received and validated ...

Страница 74: ...lies on the operation of the control circuit 1 Start ION Setup 2 Connect to your meter in advanced mode 3 Navigate to the GGIO Onboard folder and double click on the module in the righthand pane 4 Select the Setup Registers tab 5 Select the SPCS Control Mode register that corresponds to the digital output you want to control through IEC 61850 and click Edit A dialog appears 6 Select IEC 61850 CTLV...

Страница 75: ...ically COMTRADE waveform information will not be generated See the COMTRADE and ION technology technical note available from www usa siemens com pds for detailed information about COMTRADE file formats and implementation Related Topics FTP Configuring COMTRADE waveform recording using ION Setup You can enable and configure COMTRADE waveform recording using ION Setup COMTRADE is configured as part ...

Страница 76: ...e DNP Your meter can be integrated into a DNP network as a DNP slave The Distributed Network Protocol Version 3 0 DNP 3 0 is an open protocol used in the electric utility industry for communications and interoperability among substation computers Remote Terminal Units RTUs Intelligent Electronic Devices IEDs e g meters and master stations DNP supported features and default implementation Your mete...

Страница 77: ...to modify your meter s DNP port settings and default DNP map Go to www usa siemens com pds to download your meter s DNP 3 0 device profile document for detailed information on your meter s default DNP map and implementation and the Multiport DNP 3 0 and ION technology technical note for more information on how your meter supports DNP 3 0 7EN05 0336 01 77 ...

Страница 78: ...lock The clock is adjusted by synchronizing the meter s time with another time source Time synchronization messages can be automatically generated and sent to your meter from your energy management system software or other time source such as an SNTP NTP server or GPS receiver You can also manually trigger a time synchronization message from your energy management system or configuration software ...

Страница 79: ...g your meter s display Use the meter s display to configure a variety of time parameters 1 Go to Setup Menu Date Time Clock Setup Date Time Setup 2 Configure your time and date formats time zone offset and daylight savings time offset Press the down button to access the Clock Setup screen 3 Configure the clock and time synchronization source and the time synchronization time format Date Time Clock...

Страница 80: ...or UTC Specifies the time format of the time sync message UTC Coordinated Universal time for the purposes of meter configuration it is equivalent to Greenwich Mean Time GMT Local time the local time with DSTand timezone information applied Time sync source COM1 Ethernet Ethernet ION Ethernet DNP IRIG B Sets which device port accepts time synchronization messages Time synchronization messages on ot...

Страница 81: ...hreshold NTP only 1000 to 1000000 Specifies the minimum time difference in milliseconds for a time synchronization to be logged as an event This parameter can be configured to help prevent the meter s event log from being flooded with time synchronization events NTP Server Server IP address or domain name Specifies the IP address or fully qualified domain name if DNS is active of the SNTP or NTP s...

Страница 82: ... must load a meter template as part of the firmware upgrade process You can save your meter s existing framework before performing a firmware upgrade and then reload it back onto the meter if you do not want to change your meter s template Your meter s remote display and option module use firmware information from the meter but they may also need to have their internal firmware updated if internal...

Страница 83: ...for the upgrade to proceed Laptop computers generally have different default power properties than desktop computers If the laptop s hard disk shuts down or the laptop enters system standby mode this connection is broken and the upgrade procedure must be restarted If you are upgrading your meter s firmware using a laptop computer follow these guidelines Plug the laptop computer into a wall outlet ...

Страница 84: ...our meter s event log Detailed information about the option module such as serial number and firmware version is provided in the Factory module Information about the option module type and details of the option module s state is provided in the Diagnostics module See the ION Reference available from www usa siemens com pds for more information about the Factory and Diagnostic modules Loading meter...

Страница 85: ...ith an overview stating whether the firmware and framework were successfully uploaded onto your meter Loading option module firmware using ION Setup You can upload firmware to your meter s option modules using ION Setup over an Ethernet connection You can only upload firmware to the same type of module if you have different types of option modules connected to your meter you must perform the uploa...

Страница 86: ...ay firmware update BIN file You can download update files from www usa siemens com pds The remote display connected to your meter FTP access to your meter from the computer running ION Setup NOTE If your meter s remote display loses power during firmware upload the display will revert to its original firmware and you will have to reload the firmware file 1 Obtain the remote display firmware BIN th...

Страница 87: ...te Open the remote display upgrade rmdUpg folder 2 Drag the remote display firmware file into the remote display upgrade folder The file is immediately transferred to the remote display and is not stored on the meter 3 Watch your meter s display to confirm the firmware upgrade is taking place 4 Review the remote display firmware upgrade details stored in the meter s event log to confirm that the u...

Страница 88: ...cycles power to that module and all downstream modules making multiple attempts to communicate After the maximum number of communication attempts has been exceeded the meter will remove power to that module and all downstream modules When troubleshooting option modules attach each option module directly to the meter and verify its operation If each option module operates when directly connected us...

Страница 89: ...ot rely solely on data displayed on the display or in software to determine if this device is functioning correctly or complying with all applicable standards Do not use data displayed on the display or in software as a substitute for proper workplace practices or equipment maintenance Webpage interface Your meter comes with default webpages that contain typical elements A Meter type and model dev...

Страница 90: ...gs Advanced settings SNMP Parameters Configure your meter s SNMP parameters NTP Configure your meter s NTP parameters SMTP Configure your meter s SMTP parameters Date Time Configure your meter s time and time synchronization Preferences Enter your meter s nameplate information Metering Configure the parameters that impact metered data Maintenance1 Custom No default content 1By default the Maintena...

Страница 91: ...ing real time data 4 Select the main menu tab that corresponds to the category of information you want to view and select the webpage menu from the list on the left The webpage content is displayed 5 Click the webpage content headings to expand and view the meter s data 6 Select Setup to view and edit your meter s configuration Related Topics Trending and forecasting overview Security overview Vie...

Страница 92: ... Save a copy of the sample file This filename is the webpage name 4 Open your webpage in an HTML or webpage editor program 5 Modify the webpage to reference the desired meter data or parameters from the Modbus registers map and update the other fields where required 6 Save your custom webpage The meter will display translated content if it exists in the meter s memory If translated content is not ...

Страница 93: ...and how your meter processes them Sample webpage data viewing result NOTE This graphic is representative only and your meter s webpages may appear different than shown A HTML filename B Content pane title C Row heading D Units E Column heading F Named register instantaneous value G Second content pane A title Sample HTML code for data viewing webpage content Content and formatting of a data viewin...

Страница 94: ...5 table 26 div 27 h3 target sample energy localizedString Energy Readings h3 28 div id sample energy 29 table class datatable 30 tr 31 th nbsp th 32 th localizedString Present th 33 tr 34 tr 35 td localizedString Active Energy span unitsreg kWh del rec span td 36 td regname kWh del rec td 37 tr 38 tr 39 td localizedString Reactive Energy span unitsreg kVARh del rec span td 40 td regname kVARh del ...

Страница 95: ... value of the named register I a mx 20 td localizedString I b I b is the second row heading This heading is translated if possible span unitsreg I b span td This displays the units that the meter has defined for the named register I b 21 td regname I b mn td This displays the instantaneous value of the named register I b mn 22 td regname I b td This displays the instantaneous value of the named re...

Страница 96: ...s available from Siemens Industry If required your meter s ION handles document is packaged with the meter firmware file which is available for download from www usa siemens com pds Custom setup webpages must be stored on your meter s internal FTP site in the folder for Setup The custom webpage is viewed by selecting the Setup main menu tab on your meter s webpage Configuring the HTML code other t...

Страница 97: ... td nbsp td 17 tr 18 tr class minor 19 td localizedString MAC Address td 20 td regname MAC Address td 21 tr 22 tr class minor 23 td localizedString Ethernet Device Name td 24 td input name Ethernet Device Name type text td 25 tr 26 tr class minor 27 td localizedString IP Address td 28 td input name IP Address type text td 29 tr 30 table 31 32 div 33 34 h3 target sample advanced localizedString Adv...

Страница 98: ... The HTML filename including the HTML extension html This filename must comply with FTP filename conventions no spaces or special characters The filename without the HTML extension is the name shown on the webpage menu 4 form id formSampleSettings formSampleSettings is the name of the webpage content This name must be unique 7 h3 target sample basic This creates the first webpage content pane samp...

Страница 99: ...sample advanced This must match the name of the webpage content in line 34 42 td localizedString TCP Keep Alive Minutes td TCP Keep Alive Minutes is the row heading This heading is translated if possible 43 td input type text name TCP Keep Alive Minutes class small This displays the instantaneous value of the configurable named register TCP Keep Alive Minutes in a text edit field The type must mat...

Страница 100: ...t information to help identify voltage sags and swells Logged data can be retrieved by energy management software Related Topics Minimum configuration requirements for basic metering Default logging capacity Summarizes the default logging depths and intervals for your meter s onboard data and waveform recorders Data recorder number Log name Depth Interval 1 Revenue Log 3360 35 days 900 seconds 15 ...

Страница 101: ...ging of revenue values Loss Log Trg controls the frequency of Loss Compensation Data logging EgyDmd Log Trg controls the frequency of logging for the Energy and Demand Log this log is used by WinPM Net software to generate reports Hist Log Trg controls the frequency of Historic Data logging Harm Log Trg controls the frequency of Harmonics logging Programming your meter to write to any data recorde...

Страница 102: ... data logging configuration consisting of data logs set up to record values at specific intervals or on conditions Your meter s default data logging configuration should be sufficient for most applications but you can also reconfigure existing logs or create new logs for custom applications if needed Your meter can also be configured to email data log information NOTE Adding or deleting data logs ...

Страница 103: ...F lag high Ia low PF lag low Ib mean PF lead mean Ib high PF lead high Ib low PF lead low Ic mean Freq mean Ic high Freq high Ic low Freq low Loss log The Loss Log is configured to record loss values By default it logs the following values Parameter Description MU Ia 2h int Phase A interval current squared hours MU Ib 2h int Phase B interval current squared hours MU Ic 2h int Phase C interval curr...

Страница 104: ...3Avg SS1 DistV3Engy SS1 DistNominal SS1 Swell Lim SS1 Sag Lim EN50160 compliance logs The EN50160 compliance logs are used to record EN50160 compliance parameters Data recorder EN50160 component logged Data recorder EN50160 component logged EN50160 Frq Mg Power frequency and supply magnitude EN50160 PrmHrm1 Parameter data disabled by default EN50160 Hrm Vlt Harmonics EN50160 PrmHrm2 EN50160 Intrp ...

Страница 105: ...Vpos ZeroSeqComp Vzero Vpos Power Freq 4 30 10s Freq Power Frequency PqFlag 4 30 2hr Log PqFlag V1 V2 V3 V1 THD Total Harmonic Distortion V2 THD V3 THD NegSeqComp Vneg Vpos ZeroSeqComp Vzero Vpos Power Freq 4 30 3s Log PqFlag V1 V2 V3 V1 THD Total Harmonic Distortion V2 THD V3 THD NegSeqComp Vneg Vpos ZeroSeqComp Vzero Vpos 4 30 V Intrp DrtnAll Voltage interruption duration all voltages See the 4 ...

Страница 106: ...changes from off to on Your meter s event log might be used by other components of your power monitoring system Do not change the default event log configuration unless you understand the impact of the change on the power monitoring system components and the data they use and on your meter s memory Changing the default event log configuration should only be undertaken by those with an advanced und...

Страница 107: ...d in each cycle This gives you the option to record a lot of information for a very short duration or less information over a longer duration You can also configure a delay in starting waveform recording which allows you to record pre and post event data You can use your meter to detect ITI CBEMA type disturbances and can determine information regarding the magnitude and duration of each disturban...

Страница 108: ...orms recorded during a defined sag or swell event Wfm Rc I3 Sg Sw I3 current waveforms recorded during a defined sag or swell event Configuring waveform recording using ION Setup You can configure waveform recording using ION Setup For waveform recording to trigger automatically you must enter your system s nominal normal voltage and current values and then the amount of deviation from the nominal...

Страница 109: ...m recording parameters Parameter Description Sag Swell depth Specifies the number of records the sag swell data log can hold Waveform depth Specifies the maximum number of waveform records stored on the meter Waveform format Specifies the number of samples per cycle and the number of cycles that are stored in a waveform record Post event cycles Specifies the number of cycles recorded after the wav...

Страница 110: ...e value but the value is recorded in the event log You can configure the maximum learning duration The actual learning duration may vary depending on the stability of the system If the system is stable for a period equal to one quarter of the maximum learning duration learning is complete otherwise the learning period will be the maximum learning duration Example Setpoint learning duration in a st...

Страница 111: ...me Lea rned swell limit 115 Lea rned sag limit 87 See the ION Reference available from www usa siemens com pds for more information on Sag Swell Setpoint and Relative Setpoint modules Related Topics Implementing sag swell limit learning using ION Setup Implementing alarm setpoint learning using ION Setup 7EN05 0336 01 111 ...

Страница 112: ...ntrol relay operation via a hardware output device Pulser module transfers high speed pulses to a hardware pulse counting device that is used to track energy usage Calibration Pulser module integrates instantaneous power inputs then outputs high speed pulses to an LED that can be monitored for energy accuracy verification NOTE All of these modules can act as intermediaries between the physical har...

Страница 113: ...ort A B C D A1 A4 A1 A4 Port A A1 A4 Port B A1 A4 Port C A1 A4 Port D A1 A4 Option module analog input Analog Output Port A B C D Q1 Q2 S1 S6 Port A Q1 Q2 Port B Q1 Q2 Port C Q1 Q2 Port D Q1 Q2 Option module analog output NOTE When configuring your meter the configuration interface may show all of the possible ports regardless of what is physically available on your meter Related Topics Option mod...

Страница 114: ...tion module data viewing View digital I O option module data from the webpages and display To view digital option module data on your meter s display go to Inputs Outputs and select either Digital Inputs or Digital Outputs If there are no I O of the specified type an informative message is displayed To view digital option module data on your meter s webpages connect to your meter s webpages go to ...

Страница 115: ...input s zero and full scale values In most cases the output range of the sensor feeding the analog input matches the hardware limits of your meter s analog input port In that case the analog input s zero scale and full scale values are the same as the sensor s represented range For example Analog sensor Meter s analog input Analog input values 0 50 psi represented by a 4 20 mA signal 4 20 mA analo...

Страница 116: ...te signal value to send out the physical analog output port Your meter s analog I O option modules can output either low voltage or current using standard analog transducers such as 4 20 mA current transducers Related Topics Specifications Analog output behavior Your meter s analog output once configured outputs voltage or current signals If your meter s analog output source becomes unavailable N ...

Страница 117: ...t the Analog Output module and full scale and zero scale calculations Configuring option module analog outputs using ION Setup You can configure option module analog outputs using ION Setup Analog outputs are available on the optional I O modules you can connect to the base of your meter Calculate your zero scale and full scale values based on the measured value and the analog output range of your...

Страница 118: ... 2 Open the Setup Assistant for your meter 3 Navigate to I O Digital Inputs The tabs correspond to each digital input Click on the tab for the digital input you want to edit 4 Configure the digital input by selecting the parameter and clicking Edit 5 Once the parameter has been configured click OK to save the setting to the meter Parameter Value range Description Input Mode Pulse KYZ A C IRIG B1 S...

Страница 119: ...er detects an IRIG B time synchronization signal Polarity Inverting Non Inverting Specifies if the signal from the digital port is inverted or not inverted Debounce 0 000 1 000 Specifies how long in seconds the signal must remain in a state to be considered a valid state change Port Defined by your meter s hardware Your meter s physical digital input port 1 IRIG B can only be connected to one of t...

Страница 120: ... time based values such as kWh this provides the associated demand units kW for demand calculations for other values such as kg this can be configured to provide rate information kg h or kg s Mode whether a pulse is based on a complete pulse or a transition For example if each complete pulse represents 125 Wh you can configure for Wh pulsing as follows Pulse Weight pulses Wh 1 125 0 008 Unit Code ...

Страница 121: ...ntify the data within your energy management system Configuring custom input metering using ION Setup You can configure input metering with custom units and rates using ION Setup When configuring your meter the configuration interface may show all of the possible ports regardless of what is physically available on your meter NOTE Your device s digital input must be connected to the input metering ...

Страница 122: ...r example to provide on off control signals for switching capacitor banks generators and other external devices and equipment The digital output can also be used in demand synchronization applications where the meter provides pulse signals to the input of another meter to control its demand period The digital output can also be used in energy pulsing applications where a receiving device determine...

Страница 123: ...gital port is inverted or not inverted PulseWidth 0 2 000 000 Specifies the duration of the pulse in seconds Setting this parameter to 0 sets the digital output continuously on Port The physical digital output port connection Only available ports are shown 1 These parameters are only valid when pulse width is set to 0 Configuring option module digital outputs using ION Setup You can configure opti...

Страница 124: ...pulsing Energy pulsing You can configure the meter s energy pulsing LED or digital output for energy pulsing applications When the LED is set to energy pulsing the meter sends a readable pulse or signal based on the measured energy This pulse can be used for accuracy verification or as an input to another energy monitoring system You must calculate your pulse values as either pulses per kWh or as ...

Страница 125: ...Inputs outputs 9410 series 0 444 kWh sec 2 pulses per second 0 222 kWh pulse 3 Adjust for the KY giving one pulse per 2 transitions if necessary 0 222 kWh pulse 2 0 111 kWh pulse 7EN05 0336 01 125 ...

Страница 126: ...on based on a digital input s on off state Disturbance sag swell Disturbance alarms define an alarm based on a measured sag or swell Unary Unary alarms are not configurable and generate an alarm based on the meter s state for example the meter powering up Alarms have two states Active the meter detects the alarm condition is met Historical the alarm condition previously existed but the condition h...

Страница 127: ...out setpoint ΔT1 Pickup time delay period in seconds EV1 Start of alarm condition ΔT2 Dropout time delay in seconds EV2 End of alarm condition ΔT3 Alarm duration in seconds Max1 Maximum value recorded during pickup period Max2 Maximum value recorded during alarm period The meter records the date and time when the alarm event starts EV1 and when it ends EV2 The meter also performs any task assigned...

Страница 128: ...xample if you used a digital input to monitor a breaker that is always supposed to be on you would set the alarm to be active when the breaker has tripped NOTE To stop a digital alarm from being displayed set the alarm priority to Info Only Disabling force off the digital alarm off will disable all functions of the associated digital input See the ION Reference available from www usa siemens com p...

Страница 129: ...ive high Red solid bell Flash if not acknowledged Flash if not acknowledged Steady if acknowledged Flash if not acknowledged Active medium Yellow solid bell Flash if not acknowledged Flash if not acknowledged Steady if acknowledged No flash Active low Blue solid bell Flash if not acknowledged Flash if not acknowledged Steady if acknowledged No flash Historic high Red outline bell Flash if not ackn...

Страница 130: ...le digital inputs NOTE These alarms are not displayed by default Alarm information You can view information about an alarm from your meter s display Only alarms with a priority of low medium or high are displayed Parameter Description Alarm The name of the alarm for example Over THD V1 Priority Low medium or high alarm priority Date The date and time the alarm was triggered Duration The duration o...

Страница 131: ...se instructions can result in death serious injury or equipment damage Confirm your alarm is properly configured 1 Navigate to Setup Menu Alarm Setup Press the edit button to access the enable disable screen Use the up and down arrows to scroll through the available alarms Simultaneously press the up and down arrow to enable or disable the highlighted alarm 2 Press the select button to confirm you...

Страница 132: ...quality alarm for phase 2 4 30 Volt Intrp Ph3 4 30 voltage interruption power quality alarm for phase 3 Current Swell Ph1 Current swell alarms for phase 1 Current Swell Ph2 Current swell alarms for phase 2 Current Swell Ph3 Current swell alarms for phase 3 1 Any Setpoint or Relative Setpoint module with an event priority greater than the Low alarm event priority is also displayed on this screen Yo...

Страница 133: ...rm dropoff state before the alarm turns off Alarm Priority None Info Only Low Medium or High Specifies the priority level of the standard alarm To disable the alarm set priority to Info Only Custom Priority 0 255 Select custom priority to view and configure the event priority of the event associated with the alarm The event log cutoff value is displayed for reference priorities above the cutoff ar...

Страница 134: ... percentage of the nominal voltage Voltage Sag Percentage of nominal Specifies the sag limit expressed as a percentage of the nominal voltage Nominal Current 1 to 999 999 Specifies the nominal current value used for sag swell detection I Sag Pickup Numeric value Specifies the percentage the current must deviate from the nominal current in order to be classified as a sag I Sag Dropout Numeric value...

Страница 135: ...igital alarm settings 1 Start ION Setup 2 Open the Setup Assistant for your meter 3 Navigate to Alarming Digital Input 4 Configure the digital input alarm settings by selecting an input and clicking Edit Some settings are not configurable and are grayed out 5 Click Save to save the changes to the meter Parameter Value Range Description Input Input On Input Off Specifies the input state alarm behav...

Страница 136: ...nce you can have two alerts one generating an email the other sending a message to your energy management system but using the same trigger conditions or you can have two alerts with different conditions that send two unique emails to two different email addresses You can also generate alerts based on triggers from devices connected to your meter Creating alerts is an advanced feature that require...

Страница 137: ...etup This power cycles all the modules attached to your meter If you have queued firmware updates for your option modules on your meter s internal FTP site the firmware updates are performed Your option modules do not operate normally during an option module reset By default your meter is configured so that your meter automatically performs an option bus reset when needed to help keep the option m...

Страница 138: ...assword Revenue locked meters must be unlocked to perform resets that impact revenue data Your meter s digital and analog outputs may change state or may not function during resets WARNING HAZARD OF UNINTENDED OPERATION Failure to follow these instructions can result in death serious injury or equipment damage Do not use the meter for critical control or protection applications where human or equi...

Страница 139: ...tion Modules Reset Restarts all option modules attached to the meter Performing meter resets using ION Setup You can perform meter resets on your meter using ION Setup Revenue locked meters must be unlocked to perform resets that impact revenue data Meter resets clear the meter s onboard data logs and other related information NOTICE DATA LOSS Failure to follow these instructions can result in dat...

Страница 140: ...m the reset For some resets the meter indicates that the reset is in progress Do not configure or power down your meter until it indicates that the reset is complete or some parameters may not be completely reset Related Topics Revenue locking 140 7EN05 0336 01 ...

Страница 141: ...reactive components so its power factor is one PF 1 or unity power factor Inductive or capacitive loads introduce a reactive power Q component to the circuit which causes the PF to become closer to zero True PF and displacement PF The meter supports true power factor and displacement power factor values True power factor includes harmonic content Displacement power factor only considers the fundam...

Страница 142: ...vered Re a ctive powe r VAR Exporte d re ce ive d The units for power are watts W or kW for real power P vars VAR or kVAR for reactive power Q and volt amps VA or kVA for apparent power S Positive real power P flows from source to load and negative real power P flows from the load to the power source Current phase shift from voltage Electrical current can lag lead or be in phase with the AC voltag...

Страница 143: ...onfigure the minimum time between consecutive demand resets NOTE If not specified references to demand are assumed to mean power demand Peak demand reset lockout The demand reset lockout time sets the minimum time allowed between consecutive demand resets the meter ignores any attempts to reset demand that occur within the lockout period The peak demand reset lockout period is user configurable wi...

Страница 144: ...culation updates at the end of the subinterval 5 minutes 15 minu te interval WAGES monitoring WAGES monitoring allows you to record and analyze all energy sources and utilities usage Your energy system may use several different types of energy For example you may consume steam or compressed air for industrial processes electricity for lights and computers water for cooling and natural gas for heat...

Страница 145: ... energy duration for example an interval duration of three hours with an overall duration of five hours truncates the last interval duration to two hours The latest value for the specified end time is midnight 24 00 Your start time must be before the end time and after midnight and the period over which incremental energy is accumulated cannot include midnight This is because your meter s start an...

Страница 146: ...nges are made to the meter NOTE Configuring any parameter resets the incremental energy values recorded by your meter Parameter Range Description Status Enable disable Enables the incremental energy feature Start time 12 00 am to 11 59 pm The incremental energy first interval s start time The start time must be prior to the end time for energy accumulation End time 12 01 am to 12 00 am The end tim...

Страница 147: ...n this digital input is on conditional energy is accumulated NOTE It is recommended to set Assigned Input to No Connection to disable the conditional energy feature by removing any port associations 7 Click OK to save your configuration Trending and forecasting overview Trending and forecasting is a feature on your device that predicts the next set of measured or calculated data by plotting and an...

Страница 148: ...sulting information using your meter s webpages For trending and forecasting to operate your meter must have accumulated data for at least two of the specified intervals for example if you want to view a daily graph your meter must have accumulated data for at least two previous days before the present day 1 Log in to your meter s webpages 2 Click Monitoring Trending Forecasting 3 Select the Targe...

Страница 149: ...nalysis determining properly rated transformers maintenance and troubleshooting Harmonics are integer multiples of the fundamental frequency of the power system Harmonics information is required for compliance to system power quality standards such as EN50160 and meter power quality standards such as IEC 61000 4 30 Harmonics measurements include per phase magnitudes and angles relative to the fund...

Страница 150: ...he ratio of peak to RMS current values For a pure sinusoidal waveform crest factor is equal to 1 414 The meter uses the following equation to calculate crest factor Crest factor Ipe a k IRMS C Crest factor Ipeak Current peak IRMS Current RMS K factor K factor relates the heating effect of a distorted current in a transformer to a sinusoidal current with the same RMS magnitude it describes a transf...

Страница 151: ...al system thd HC RMS 100 TDD HC DemandMax 100 This is an advanced procedure that should only be performed by users with an advanced knowledge of power quality ION architecture and the power system being monitored See the ION Reference available from www usa siemens com pds for details about the Harmonics Measurement module Phasors Phasors are used to represent the voltage and current relative magn...

Страница 152: ... when used in a system of disturbance direction detection devices as shown in the diagram below Utility Meter 1 Meter 2 Power consu mer A Disturbance location B Meter 1 reports downstream disturbance C Meter 2 reports upstream disturbance D Meters report upstream disturbance E Meter reports downstream disturbance The arrows show the direction the meters have determined for the disturbance With thi...

Страница 153: ...ality 9410 series See the ION Reference available from www usa siemens com pds for more detailed information about the Disturbance Direction Detection module Related Topics Event log overview 7EN05 0336 01 153 ...

Страница 154: ...in order to conduct accuracy verification testing Refer to your meter s installation documentation for power supply specifications DANGER HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH Failure to follow these instructions will result in death or serious injury Verify the device s power source meets the specifications for your device s power supply Control equipment Control equipment is required f...

Страница 155: ...eference device or energy standard should be warmed up as recommended by its manufacturer NOTE Verify the accuracy and precision of all measurement equipment used in accuracy testing for example voltmeters ammeters power factor meters Energy pulsing Your meter has energy pulsing LEDs and a digital output that can be used for energy pulsing Your meter has energy pulsing LEDs one visible light and o...

Страница 156: ...roperly rated voltage sensing device to confirm that all power is off Do not exceed the device s ratings for maximum limits Verify the device s power source meets the specifications for your device s power supply 1 Turn off all power supplying this device and the equipment in which it is installed before working on the device or equipment 2 Use a properly rated voltage sensing device to confirm th...

Страница 157: ...accuracy verification on the test points Run each test point for at least 30 seconds to allow the test bench equipment to read an adequate number of pulses Allow 10 seconds of dwell time between test points Calculate the number of required pulses The reference test equipment typically requires you to specify the number of pulses required for a test duration of t seconds Normally the number of puls...

Страница 158: ...ltage or current circuits often caused by worn out contacts or terminals Inspect terminals of test equipment cables test harness and the meter under test Meter ambient temperature is significantly different than 23 C 73 F Floating ungrounded neutral voltage terminal in any configuration with unbalanced phase voltages Inadequate meter control power resulting in the meter resetting during the test p...

Страница 159: ...ency at 0 50 lagging power factor current lagging voltage by 60 phase angle VAR hour test point Sample accuracy verification test point Full load 100 to 200 of the nominal current 100 of the nominal voltage and nominal frequency at zero power factor current lagging voltage by 90 phase angle Light load 10 of the nominal current 100 of the nominal voltage and nominal frequency at zero power factor c...

Страница 160: ...ntities after the meter is locked Refer to the installation guide shipped with your meter and accessories regarding the installation of these security features Revenue firmware security features Your revenue specific meter has additional firmware security features You can only upgrade to revenue qualified firmware and frameworks Your firmware upgrade files have digital signature confirmation to he...

Страница 161: ...nstructions Revenue locking Revenue locking your meter helps prevent modifications to revenue related settings and data on your meter or tampering with your meter s voltage and current connections Revenue locking may be required to help meet government regulations and utility security requirements or can be used to help ensure the validity of revenue data Download the ION Device Template Reference...

Страница 162: ...e it is firmly in place 7 Seal the revenue lock switch cover if required PT CT correction PT CTcorrection also called instrument transformer correction can help reduce the need to replace transformers in installations where high accuracy is required The primary application for PT CT potential transformer current transformer correction is to apply correction factors for ratio errors and phase angle...

Страница 163: ... can view the TOU active rates and seasons through your meter s display See the ION Setup online help available from www usa siemens com pds for instructions on how to configure time of use on your meter See the ION Reference available from www usa siemens com pds for a description of the Time of use module and its settings Related Topics Data viewing using your meter s display 7EN05 0336 01 163 ...

Страница 164: ... TFT LCD 320 x 240 resolution Display backlight White LED Viewable area 70 6 x 52 9 mm 2 78 x 2 08 in Keypad 5 button Maximum number of option modules 4 based on mechanical stress and required IP rating 9410TC DIN meter Mounting position Horizontal TS35 DIN rail IP degree of protection Meter body IP30 except connectors Maximum number of option modules 4 based on mechanical stress and required IP r...

Страница 165: ...ltage inputs Maximum VT PT primary 1 0 MV AC Specified accuracy range 57 to 400 V L N 100 to 690 V L L Wye or 100 to 600 V L L Delta Specified accuracy frequency 42 to 69 Hz 50 60 Hz nominal Current inputs Specified accuracy current range 50 mA 10 A AC control power Operating range 50 60 Hz 10 90 to 415 V AC L N 10 400 Hz 90 to 120 V AC 10 Ride through time 100 ms 6 cycles at 60 Hz min any conditi...

Страница 166: ...ms Current draw ON 2 5 mA OFF 0 5 mA Environmental characteristics Operating temperature 25 ºC to Max temp 13 ºF to Max temp Maximum operation temperature is based on the quantity and type of attached option modules See Maximum operating temperature page 166 Storage temperature 40 to 85 C 40 to 185 F Humidity rating 5 95 RH non condensing Maximum dewpoint 37 C 99 F Pollution degree 2 Altitude 3000...

Страница 167: ...00 4 11 Immunity to magnetic fields IEC 61000 4 8 Immunity to ring waves IEC 61000 4 12 Immunity to conducted disturbances 2 150 kHz CLC TR 50579 Radiated and conducted emissions FCC part 15 Class B EN55011 EN55022 Class B ICES 003 Class B Surge withstand capacity SWC ANSI C37 90 1 Mechanical compliance Vibration IEC 60068 2 6 Shock IEC 60068 2 27 Safety Safety construction IEC EN 61010 1 ed 3 CAT...

Страница 168: ...p time Minimum 7 years under specified storage conditions Remote display IP degree of protection Front IP54 Rear IP30 Cable CAT5 5e UTP use unshielded connector only Mounting position Vertical Display type 1 4 VGA color graphic TFT LCD 320 x 240 resolution Display backlight White LED Viewable area 70 6 x 52 9 mm 2 78 x 2 08 in Keypad 5 button Option modules US2 948M2AO4AI Analog 2 out 4 in Maximum...

Страница 169: ... environment E2 Cover sealing type Wire and crimp Applicable measurements Active import export energy metering System types for MID compliant applications 3 phase 4 wire Wye grounded 3 phase 3 wire Delta ungrounded Current rating 0 05 5 10 A Nominal frequency 50 Hz Energy pulsing LED Pulse weight 5000 imp kWh To comply with European directive MID 2004 22 EC the meter must be installed in MID certi...

Страница 170: ...9410 series Specifications 170 7EN05 0336 01 ...

Страница 171: ...Specifications 9410 series 7EN05 0336 01 171 ...

Страница 172: ...y Norcross GA 30092 USA For more information visit www usa siemens com pds Search for the nearest sales office at www usa siemens com pds or call 1 800 241 3138 Contact the Power Distribution Solutions PDS Service and Support at Operating hours 8 00 am 5 00 pm EST Monday Friday Phone 1 800 333 7421 www usa siemens com pds ...

Отзывы: