Logging
9410 series
Parameter
Description
kWh del int
Interval kWh delivered
kWh rec int
Interval kWh received
kVARh del int
Interval kVARh delivered
kVARh rec int
Interval kVARh received
Historic data logs
Three historic data logs are used to record standard power system quantities, such as
phase current, phase voltage and power factor. These logs are labeled Hist Mean Log,
Hist High Log, and Hist Low Log. By default, they log the following values:
Hist Mean Log
Hist High Log
Hist Low Log
Vll ab mean
I avg mean
Vll ab high
I avg high
Vll ab low
I avg low
Vll bc mean
I 4 mean
Vll bc high
I 4 high
Vll bc low
I 4 low
Vll ca mean
kW tot mean
Vll ca high
kW tot high
Vll ca low
kW tot low
Vll avg mean
kVAR tot
mean
Vll avg high
kVAR tot high
Vll avg low
kVAR tot low
V unbal mean
kVA tot mean
V unbal high
kVA tot high
V unbal low
kVA tot low
Ia mean
PF lag mean
Ia high
PF lag high
Ia low
PF lag low
Ib mean
PF lead mean
Ib high
PF lead high
Ib low
PF lead low
Ic mean
Freq mean
Ic high
Freq high
Ic low
Freq low
Loss log
The Loss Log is configured to record loss values. By default, it logs the following
values:
Parameter
Description
MU Ia^2h int
Phase A interval current squared hours
MU Ib^2h int
Phase B interval current squared hours
MU Ic^2h int
Phase C interval current squared hours
MU Vllab^2h int
Phase A interval voltage Line-to-Line squared hours
MU Vllbc^2h int
Phase B interval voltage Line-to-Line squared hours
MU Vllca^2h int
Phase C interval voltage Line-to-Line squared hours
MU Vln a^2h int
Phase A interval voltage Line-to-Neutral squared hours
MU Vln b^2h int
Phase B interval voltage Line-to-Neutral squared hours
MU Vln c^2h int
Phase C interval voltage Line-to-Neutral squared hours
Harmonics logs
Two harmonics logs record various harmonics data, including K-factor and Total
Harmonic Distortion (THD). These recorders are labeled Harm Mean Log and Harm
High Log. By default, they log the following values:
7EN05-0336-01