Number of masters / Number of slaves
When using the "Standard/DP" and "Universal" profiles, you can specify the number of
masters and slaves in the network in these two input boxes. The number of masters and
slaves is used for calculating the bus parameters in the network.
Permissible value ranges for these profiles:
–
Number of masters: 0..126
–
Number of slaves: 0..126
If you are using the "User-defined" profile, the two input boxes are disabled. In this case,
the boxes have a fixed presetting:
–
Number of masters: 1
–
Number of slaves: 126
Bus parameters
The parameters (see table) that describe the properties of the PROFIBUS subnet are mostly
preset:
●
The bus parameters are fixed or are calculated from them with the use of the
"Standard/DP" "Universal" profiles.
●
If you are using the "User-defined" profile, you can configure some bus parameters.
Note
Configuring the bus parameters
We recommend applying the values already set in the connected PROFIBUS network for the
bus parameters.
Bus parameter
Range of values *
(default setting) **
Meaning ***
Tslot
815/995...16383 *
(100...3000)
Slot time [t_Bit]
The slot time specifies the maximum length of time the sender will wait for a
response from an addressed partner.
For the calculation, the following parameters which have an effect on the
bus hardware are used as basis:
•
Cable length: 1...1100 m
•
Number of repeaters: 0...10
Max. Tsdr
76...1023 *
(55...980)
Maximum protocol processing time [t_Bit]
The maximum protocol processing time specifies the maximum time al-
lowed for the responding station to answer.
Max. Tsdr must be less than the slot time.
Min. Tsdr
11...75 *
(11...150)
Minimum protocol processing time [t_Bit]
The minimum protocol processing time specifies the minimum amount of
time after which the responding station can answer.
Содержание 6GK1411-1AC00
Страница 10: ...Table of contents SIMATIC CC7 10 Operating Instructions 10 2019 C79000 G8976 C503 02 ...
Страница 30: ...LEDs Connectors Buttons CLP 2 4 CLP Slot SIMATIC CC7 30 Operating Instructions 10 2019 C79000 G8976 C503 02 ...
Страница 136: ...Dimension drawings SIMATIC CC7 136 Operating Instructions 10 2019 C79000 G8976 C503 02 Figure 8 2 Side view ...
Страница 150: ...Index SIMATIC CC7 150 Operating Instructions 10 2019 C79000 G8976 C503 02 ...