In other areas, the fuse must meet the following requirements:
–
Suitable for DC (min. 60 V / max. 3 A)
–
Breaking current > highest possible current of the current source (incl. short circuit
current and fault)
–
Approval according to IEC/EN 60934
–
Breaking characteristics: Max. 120 s at 2 x I
n
You do not need a fuse for the power supply cable if you use a voltage source according to
NEC Class 2 or a power supply from the range of accessories, see appendix Power supply
(Page 137).
Recommendation: Use the power supply of a process station if this is in the vicinity of the
gateway.
Note
Protective ground
A PELV circuit contains a connection to protective ground. Without a connection to protective
ground, or in case there is a fault in the connection to the protective ground, the voltage for
the circuit is not stabilized.
NOTICE
Fuses for the cables of the digital output (corresponds to "Limited Energy")
The current on the terminal must not exceed 1 A. Use a fuse for the power supply that
protects against currents > 1 A.
The fuse has to be designed for protection of DC power supply circuits as well as for the
following requirements.
•
In areas subject to the NEC or CEC, the fuse must meet the following requirements:
–
Suitable for DC (min. 60 V / max. 1 A)
–
Breaking current min. 10 kA
–
UL/CSA listet (UL 248-1 / CSA 22.2 No. 248.1)
–
Classes R, J, L, T or CC
•
In other areas:
–
Suitable for DC (min. 60 V / max. 1 A)
–
Breaking current min. 10 kA
–
Approved for power supply circuits (branch circuits) according to local regulations
(e.g. IEC 60127-1, EN 60947-1)
–
Breaking characteristics: B or C circuit breakers and fuses
Содержание 6GK1411-1AC00
Страница 10: ...Table of contents SIMATIC CC7 10 Operating Instructions 10 2019 C79000 G8976 C503 02 ...
Страница 30: ...LEDs Connectors Buttons CLP 2 4 CLP Slot SIMATIC CC7 30 Operating Instructions 10 2019 C79000 G8976 C503 02 ...
Страница 136: ...Dimension drawings SIMATIC CC7 136 Operating Instructions 10 2019 C79000 G8976 C503 02 Figure 8 2 Side view ...
Страница 150: ...Index SIMATIC CC7 150 Operating Instructions 10 2019 C79000 G8976 C503 02 ...