Configuration
4.7 Process access
SIMATIC CC7
Operating Instructions, 10/2019, C79000-G8976-C503-02
65
The following standard TSAP IDs are used:
–
Local TSAP of the gateway: 01.01
–
Remote TSAP of the controller family:
- S7-1200/1500: 02.01
- S7-300/400: 03.02
Disable the option if the remote TSAPs do not match the preset standard TSAPs. In this
case, configure the TSAP that is assigned in the STEP 7 project.
●
Local TSAP
Range of values: 01.01 ... 7E.7E
We recommend using the default TSAP (01.01).
●
Remote TSAP
Enter the TSAP of the S7 connection assigned in STEP 7 at the station end if you have
configured a connection with an unspecified partner in the CPU for the gateway.
When using a configured unspecified connection, disable the "Active connection
establishment" option in STEP 7.
●
Polling cycle (ms)
Cycle time in milliseconds in which the gateway reads the data from the station.
Range of values: 50...100 000 000
Note: If you transfer large volumes of data, the actual cycle time may be longer than
configured.
S7 PROFIBUS
Only for CC716
The gateway and the SIMATIC S7 station communicate over S7 PROFIBUS connections.
The gateway is the active station.
Requirements:
The same requirements apply as described in section "S7 Ethernet" above.
Parameters:
●
PROFIBUS address
PROFIBUS address of the S7 station (gateway communication partner)
●
Controller family
Select the controller family of the connected station from the drop-down list:
–
S7-1200/1500
–
S7-300/400
Содержание 6GK1411-1AC00
Страница 10: ...Table of contents SIMATIC CC7 10 Operating Instructions 10 2019 C79000 G8976 C503 02 ...
Страница 30: ...LEDs Connectors Buttons CLP 2 4 CLP Slot SIMATIC CC7 30 Operating Instructions 10 2019 C79000 G8976 C503 02 ...
Страница 136: ...Dimension drawings SIMATIC CC7 136 Operating Instructions 10 2019 C79000 G8976 C503 02 Figure 8 2 Side view ...
Страница 150: ...Index SIMATIC CC7 150 Operating Instructions 10 2019 C79000 G8976 C503 02 ...