Modbus/TCP
The gateway and the Modbus station communicate over Modbus/TCP connections. The
gateway is the active partner during connection setup.
●
RTU number
RTU number of the Modbus slave
●
IP address
IPv4 address of the station interface
●
Port number
Port number of the station interface. Default: 502
●
Connection establishment attempts
Maximum number of attempts to establish a connection to a station.
After reaching the configured number of attempts, no additional connection attempts are
made until the gateway is restarted.
Range of values: -1...32768
With "-1" the number of connection attempts is unlimited.
●
Polling interval (s)
Cycle time in seconds in which the gateway reads the data from the station.
Range of values: 1...65535
●
Reconnection delay (s)
Wait time (seconds) before a new connection attempt is made when the station cannot be
reached or the connection is terminated.
A wait time makes sense, for example, to wait for short-term network faults to be removed
or restart of a station.
Range of values: 0...100
●
Timeout (ms)
When the gateway does not receive a response from the station within the configured
time (milliseconds), it repeats the station request.
Range of values: 100...65535
●
Max. number of faulty responses
Maximum number of outstanding or faulty station responses.
When reaching the maximum number, the gateway considers the station to be faulty and
terminates the connection. When a connection is terminated, the gateway tries to re-
establish the connection.
Range of values: 1...32
●
Retries
Maximum number of retries of the station query when the gateway does not receive any
or a faulty response from the station.
Range of values: 0...10
Содержание 6GK1411-1AC00
Страница 10: ...Table of contents SIMATIC CC7 10 Operating Instructions 10 2019 C79000 G8976 C503 02 ...
Страница 30: ...LEDs Connectors Buttons CLP 2 4 CLP Slot SIMATIC CC7 30 Operating Instructions 10 2019 C79000 G8976 C503 02 ...
Страница 136: ...Dimension drawings SIMATIC CC7 136 Operating Instructions 10 2019 C79000 G8976 C503 02 Figure 8 2 Side view ...
Страница 150: ...Index SIMATIC CC7 150 Operating Instructions 10 2019 C79000 G8976 C503 02 ...