Configuration
4.10 Data points
SIMATIC CC7
106
Operating Instructions, 10/2019, C79000-G8976-C503-02
●
Time trigger
For time triggers, select the value of the cycle and the respective unit of time from the
drop-down list.
–
Cyclic
The value of the data point is transferred cyclically. Ranges of values:
100 .. 100 000 000 ms
1 .. 1 000 000 s
1 .. 1666 min
1 .. 27 h
–
Once daily
The value is transferred once a day at the configured time.
–
Once weekly
The value is transferred once a week.
–
Once monthly
The value is transferred once a month.
If a month has fewer days than the day specified in the configuration, the value of the
data point is transferred at the end of the month.
●
Value trigger
Select the type using the drop-down list and add the respective values.
The value ranges of the value triggers depend on the data type of the data point.
–
Deviation
The value is transferred as soon as it changes compared to the value that was read in
before.
–
Area outside
The value is transferred as soon as it is outside the configured area.
–
Area within
The value is transferred as soon as it is inside the configured area.
–
Threshold HIGH
The value is transferred as soon as it exceeds the configured value.
–
Threshold LOW
The value is transferred as soon as it drops below the configured value.
Note:
The range of values of the station data point is converted to the range of values of the
device data point.
●
Input trigger
–
Digital input
Transfer once upon edge change at the digital input
Alternatively with edge change 1
→
0 or 0
→
1
Содержание 6GK1411-1AC00
Страница 10: ...Table of contents SIMATIC CC7 10 Operating Instructions 10 2019 C79000 G8976 C503 02 ...
Страница 30: ...LEDs Connectors Buttons CLP 2 4 CLP Slot SIMATIC CC7 30 Operating Instructions 10 2019 C79000 G8976 C503 02 ...
Страница 136: ...Dimension drawings SIMATIC CC7 136 Operating Instructions 10 2019 C79000 G8976 C503 02 Figure 8 2 Side view ...
Страница 150: ...Index SIMATIC CC7 150 Operating Instructions 10 2019 C79000 G8976 C503 02 ...