SIMATIC CC7
Operating Instructions, 10/2019, C79000-G8976-C503-02
141
Syslog messages
C
Security events
The gateway outputs Syslog messages according to RFC 5424. The messages are based
on IEC 62443-3-3.
C.1
Structure of the messages
C.1.1
Structure of the Syslog messages
Syslog messages record changes in device states as status information. Syslog messages
according to RFC 5424 or RFC 5426 are output by devices and transferred to a server via
the set UDP port (standard: 514). The Syslog server collects the information of the devices
and informs you about these events.
The Syslog protocol prescribes a fixed sequence and structure of the possible parameters.
Syslog messages according to RFC5424 have the following structure:
Part / Parameter
Explanation
HEADER
PRI
Priority of the Syslog message, divided into:
•
Severity (Severity)
Possible values:
–
0 Emergency
–
1 Alert
–
2 Critical
–
3 Error
–
4 Warning
–
5 Notice
–
6 Information
–
7 Debug
•
Facility (Origin)
Possible values, e.g.: Sub-system, service, user
VERSION
Version number of the Syslog specification
TIMESTAMP
Time stamp of the device as local time including time zone and correction for daylight sav-
ing/standard time
Format: YYYY-MM-DDThh:mm:ss.mxx:yy
Example: 2010-01-01T02:03:15.0003+02:00
Содержание 6GK1411-1AC00
Страница 10: ...Table of contents SIMATIC CC7 10 Operating Instructions 10 2019 C79000 G8976 C503 02 ...
Страница 30: ...LEDs Connectors Buttons CLP 2 4 CLP Slot SIMATIC CC7 30 Operating Instructions 10 2019 C79000 G8976 C503 02 ...
Страница 136: ...Dimension drawings SIMATIC CC7 136 Operating Instructions 10 2019 C79000 G8976 C503 02 Figure 8 2 Side view ...
Страница 150: ...Index SIMATIC CC7 150 Operating Instructions 10 2019 C79000 G8976 C503 02 ...