Installation, wiring, commissioning
3.3 Connecting
SIMATIC CC7
Operating Instructions, 10/2019, C79000-G8976-C503-02
43
4.
CC716:
If necessary, connect the cable for the digital input/output to the terminal block of the
device.
–
Always wire the digital input and output in pairs.
–
The maximum permitted cable length is 30 m.
For information on the position of the terminals, see section Digital Input / Output
5.
Turn the power supply on only after the device has been completely wired and
connected.
The further procedure is described in the section Commissioning (Page 44).
Terminal blocks for digital input/output and power supply
The plug-in terminal blocks for the sockets have mechanical reverse polarity protection.
You can find additional technical details in the section Technical specifications (Page 125).
Digital input/output (CC716)
Table 3- 1
Assignment of the sockets for the digital input (DI) and digital output (DQ)
Terminal
Assignment
DI+
DC 24 V / 1 A
DI- (ground)
-
DO+
DC 24 V / 1 A
DO-
-
Power supply
Note
The power supply unit of the device is not electrically isolated.
Use only copper cables for the power supply.
Table 3- 2
Pin assignment of the socket for the power supply
Terminal
Assignment
L1+
DC 24 V
M1
Reference ground
M2
Ground reference for redundant connection
L2+
24 V DC for redundant connection (optional)
Functional earth
Содержание 6GK1411-1AC00
Страница 10: ...Table of contents SIMATIC CC7 10 Operating Instructions 10 2019 C79000 G8976 C503 02 ...
Страница 30: ...LEDs Connectors Buttons CLP 2 4 CLP Slot SIMATIC CC7 30 Operating Instructions 10 2019 C79000 G8976 C503 02 ...
Страница 136: ...Dimension drawings SIMATIC CC7 136 Operating Instructions 10 2019 C79000 G8976 C503 02 Figure 8 2 Side view ...
Страница 150: ...Index SIMATIC CC7 150 Operating Instructions 10 2019 C79000 G8976 C503 02 ...