Configuration
4.10 Data points
SIMATIC CC7
Operating Instructions, 10/2019, C79000-G8976-C503-02
105
Trigger
You use the triggers to specify the conditions that initiate the transfer of the value saved in
the device to the broker.
Up to two triggers can be selected per data point. The following trigger classes can be
configured:
●
Time trigger
–
Cyclic
Cyclic transmission - configurable cycle
–
Time
Once daily / Once weekly / Once monthly
●
Value trigger
–
Deviation: Transmission in case of deviation from the last stored value
–
Threshold LOW: Transmission if value is below the threshold
–
Threshold HIGH: Transmission if value is above the threshold
–
Range within: Transmission when the value enters a value range
–
Range outside: Transmission when the value leaves a value range
●
Input trigger
–
Digital input
Transfer upon edge change at the digital input
You can combine two triggers for each data point. When two triggers are configured, the
transfer is initiated as soon as one of the two trigger conditions is met.
Not all trigger types can be combined for a tag in practice. The following trigger combinations
are supported:
Permitted trigger combinations
Trigger 1
Trigger 2
Cyclic
Value trigger
Time
-
Value trigger
Cyclic
Input trigger
Value trigger
Additional restrictions can result from the trigger types supported by the individual data
types; see "Data types" table below.
Trigger 1 / Trigger 2
The following types of triggers are available:
Содержание 6GK1411-1AC00
Страница 10: ...Table of contents SIMATIC CC7 10 Operating Instructions 10 2019 C79000 G8976 C503 02 ...
Страница 30: ...LEDs Connectors Buttons CLP 2 4 CLP Slot SIMATIC CC7 30 Operating Instructions 10 2019 C79000 G8976 C503 02 ...
Страница 136: ...Dimension drawings SIMATIC CC7 136 Operating Instructions 10 2019 C79000 G8976 C503 02 Figure 8 2 Side view ...
Страница 150: ...Index SIMATIC CC7 150 Operating Instructions 10 2019 C79000 G8976 C503 02 ...