4 GET TO KNOW SAFERS3
4.7.3
Dynamic system configuration activation
The dynamic system configuration can be activated through the digital inputs or the
safety Fieldbus (if available). One activation method excludes the other and activation
through digital inputs has priority over activation through Fieldbus.
4.7.4
Dynamic configuration through the digital inputs
To activate the dynamic system configuration, one or both the digital inputs of the
control can be used. The result is the following:
If...
Then it is possible to dynamically switch
between...
only
one
digital input is used for the dynamic
configuration
two
preset configurations (see
and
)
both
digital inputs are used for the dynamic
configuration
four
preset configurations (see
Note
: the change of configuration is safe because it is activated by two-channel inputs.
Example 1
The first digital input has been linked to the dynamic configuration.
Dynamic
configuration
number
Input 1
Input 2
#1
0
-
#2
1
-
0 = signal deactivated; 1 = signal activated
Example 2
The second digital input has been linked to the dynamic configuration.
Dynamic
configuration
number
Input 1
Input 2
#1
-
0
#2
-
1
0 = signal deactivated; 1 = signal activated