22
O P E R A T I N G I N S T R U C T I O N S | safeRS3
8027489/2022-03-01 | SICK
Subject to change without notice
4 GET TO KNOW SAFERS3
Part
Description
Control
J
Power supply LEDs (steady green)
safeRS3 Control
PROFINET,
safeRS3 Control
I/O
K
CAN bus terminal block for connecting the first sensor safeRS3 Control
PROFINET,
safeRS3 Control
I/O
L
DIP switch to turn on/off the bus termination
resistance:
l
On (top position, default) = resistance included
l
Off (bottom position)= resistance excluded
safeRS3 Control
PROFINET,
safeRS3 Control
I/O
M
CPU LEDs:
l
on the right: status of hardware functions of the
primary micro-controller
l
off: normal behavior
l
steady red: contact Technical Support
safeRS3 Control
PROFINET,
safeRS3 Control
I/O
N
Ethernet Fieldbus port n. 1 with LEDs
safeRS3 Control
PROFINET
O
Ethernet Fieldbus port n. 2 with LEDs
safeRS3 Control
PROFINET
4.2.4
System status LEDs
The LEDs are each dedicated to a sensor, and can display the following statuses:
Status
Meaning
Steady green
Normal sensor function and no motion detected
Orange
Normal sensor function and some motion detected
Flashing red
Sensor in error (see
Steady red
System error (see
)
Flashing green
Sensor in boot status (see
)
4.2.5
Fieldbus status LEDs
The LEDs reflect the status of the PROFINET/PROFIsafe Fieldbus and their meaning is
reported below.
Note
: F1 is the LED at the top, F6 is the LED at the bottom.
LED
Status
Meaning
F1 (power)
Steady green
Normal behavior
Flashing green
or off
Contact Technical Support
F2 (boot)
Off
Normal behavior
Steady or
flashing yellow
Contact Technical Support